Installation steps (fixed UVC):


1.
The fixed UV-C lamps are located on the front of the
UV-C drawer on Base Unit.

2.
Install the lamps into the two open holes on the front
of the drawer. Line up the screw holes on white
ceramic base of the lamp to those on the drawer.
Tighten screws so that the gasket is sealed.

Note: The T3 UV lamp assembly can be removed
independently, simply by removing the 2 screws in
the white lamp holder.


3.
Plug the rubber lamp connector fully onto the
installed

UV lamp assembly. Be sure the 4 pinholes are

orientated properly to the 4 mating pins of the lamp.

Note: the pins are in a rectangular patent and can
only be mated in 2 positions. Pulling the lamp boot
back will help with the visual alignment of the pins
and connections. After making the connection be
sure to push lamp boot over lamp base.

See the illustration of the T3 lamp 4-pin connector.

22

Installation Requirements


This unit is designed to power up constantly and
should not cycle on and off with a blower motor.

The desired location for installation of the Ultravation
Base Unit Media Air Cleaner is in the return air under the
blower compartment. In this location, the blower motor
and internal components will be kept clean.

Once the Ultravation Base Unit Media Air Cleaner is
installed, it is very important to maintain the unit by
changing the filter periodically (typically in 6 mo intervals)
so as not obstruct airflow, damage components or
increase energy costs.

The Ultravation Base Unit Media Air Cleaner has been
designed for use in conjunction with virtually any air
handler system.

Do not install this unit in the supply duct.

Be sure to plan adequate space for filter and lamp
replacement.

Before installation is complete, seal all joints and seams
with duct tape or caulking.

Notice:

All wiring inside of the duct or air handling system in
direct line of site of the UV lamp must be shielded with
aluminum foil or equivalent non-combustible material.
When installing this unit, select a mounting location that
prevents ultraviolet light exposure to plastic flexible duct
liner or other plastic components with unknown
resistance to ultraviolet light. Ultraviolet light may cause
color shift or structural degradation of plastic HVAC
components.