Warning, Connecting electric dryers (cont.) usa only – LG DLEX3550V User Manual

Page 26

Advertising
background image

26

InstallatIon InstrUCtIons

InstallatIon InstrUCtIons

Connecting electric dryers (cont.)

USA only

w

WarnInG

Connect the power cord to the terminal block. Each colored

wire should be connected to same color screw. Wire color

indicated on manual is connected to the same color screw

in block. Failure to follow these instructions may result in a

short or overload.

Grounding through the neutral conductor is prohibited

for: (1) new branch-circuit installations, (2) mobile homes,

(3) recreational vehicles, and (4) areas where local codes

prohibit grounding through the neutral conductor.

three-wire connection for electric dryers:

power cord

• A 3-wire connection is NOT permitted on new construction after

January 1, 1996.

• A UL-listed strain relief is required.

1. Remove the terminal block access cover on the upper back of

the dryer. Install a UL-listed strain relief into the power cord
through-hole; then thread a UL-listed, 30 A, 240 V, 3-wire, #10
AWG-minimum copper
conductor power cord through the
strain relief.

• Use a 30 A, 240 V, UL-listed power cord with #10 AWG-

minimum copper conductor and closed loop or forked

terminals with upturned ends.

2. Attach the two hot leads of the power cord to the outer

terminal block screws. Attach the neutral wire to the center

terminal block screw. Connect the external ground (if required

by local codes) to the green ground screw. TIGHTEN ALL

SCREWS SECURELY. Reinstall the terminal block access cover.

UL-Listed

3-Wire

Power Cord

UL-Listed

Strain Relief

Terminal Block

Ground Screw

Ground Wire

Hot

(Black)

Hot

(Red)

Neutral

(White)

Neutral

Grounding wire

MFL67408101_en_110923.indd 26

2011.9.23 11:8:5 AM

Advertising
This manual is related to the following products: