Using Thermostat

Emergency Operation

• Definition of terms

- Trouble : a problem which can stop system operation, and can be resumed temporally under

limited operation without certificated professional's assist.

- Error : problem which can stop system operation, and can be resumed ONLY after certificated

professional's check.

- Emergency mode : temporary heating operation while system met Trouble.

• Objective of introducing 'Trouble'

- Not like airconditioning product, hydro kit is generally operated in whole winter season without

any system stopping.

- If system found some problem, which is not critical to system operating for yielding heating

energy, the system can temporarily continue in emergency mode operation with end user's
decision.

• Classified Trouble

- Trouble is classified into two levels according to the seriousness of the problem : Slight Trouble

and Heavy trouble

- Slight Trouble : a problem is found inside the indoor unit. In most case, this trouble is concerned

with sensor problems. The outdoor unit is operating under emergency mode operation condition
which is configured by DIP switch No. 4 of the indoor unit PCB.

- Heavy trouble : a problem is found inside the outdoor unit.

- Option Trouble : a problem is found for option operation such as water tank heating. In this

trouble, the troubled option is assumed as if It does not cause in the Product.

• Emergency operation level

- When system met trouble, it stops operation and waits for userʼs decision : Calling service center

or starting emergency operation.

- To start emergency operation, user simply pushes ON / OFF button once more.

- Two different levels are prepared for emergency operation : High temperature cycle and low

temperature cycle.

- In emergency operation mode, user can not adjust target temperature.

22 Hydro Kit

DIP

Switch

Target

Leaving Water

Temperature

Target

Room Air

Temperature

Target

Sanitary Water

Temperature

High temperature cycle

OFF

50℃(122℉)

24℃(75℉)

50℃(122℉)

Low temperature cycle

ON

30℃(86℉)

19℃(66℉)

50℃(122℉)