Configuration menu – Aube Technologies AUBE NON-PROGRAMMABLE H/C CONTROLLER TH146-N-U User Manual

Page 8

Advertising
background image

TH146-N-U

8/12

Configuration Menu

Item

HP

HVAC

Parameters

Display

Options

Default

Description

1

Temperature format

°C / °F

°C

Select the temperature display format.

2*

Balance point low

-30 to 10°C

(-22 to 50°F)

-10°C

(14°F)

Set the bP L limit (see section 4.2).
NOTE: Lower bP L below its minimum (- -) if you do not wish to use this
function.

3*

Balance point high

-5 to 30°C

(23 to 86°F)

5°C

(41°F)

Set the bP H limit (see section 4.2).
NOTE: Raise bP H above its maximum (- -) if you do not wish to use this
function.

4*

Defrost point

-10 to 15°C

(14 to 59°F)

10°C

(50°F)

Set the defrost point temperature (see section 4.3).
NOTE: Raise the defrost point above its maximum (- -) if you do not wish to
use this function.

5*

Installation type

Ad / nr

Ad

Set according to the type of heat pump installation (see section 4.4).

Ad (add-on): Use this setting when the indoor coils are located down-
stream of the auxiliary heat source. This is generally the case for add-on
installations.

nr (normal): Select this setting when the indoor coils are located
upstream of the auxiliary heat source. This is generally the case for new
installations.

6*

Auxiliary

interstage delay

5 to 90 min.

30 min.

Set the interstage delay for the auxiliary stage (see section 4.5).

7

Low temperature limit

-10 to 20°C

(14 to 68°F)

- -

Set the low temperature limit of the plenum (see section 4.6).
NOTE: This function is not used if you lower LLMT below its minimum (- -)
or if the plenum temperature sensor is not connected to the controller.

8

High temperature limit

30 to 90°C

(86 to 194°F)

- -

Set the high temperature limit of the plenum (see section 4.6).
NOTE: This function is not used if you raise HLMT above its maximum (- -)
or if the plenum temperature sensor is not connected to the controller.

9

Cycles per hour

2 to 6

4

Select the number of heating/cooling cycles per hour. For optimal heating
control, use the setting that matches your system as follows: 3=20 min (hot
water, 90%+ high-efficiency furnace), 4=15 min (gas or oil), 5=12 min (gas
or oil), 6=10 min (electric).

10

Heat type

GA / EL

EL

This setting determines the fan operation in automatic mode when the sys-
tem is in heating mode (see section 5.2).

EL (electric heating): The fan starts when heating starts and stops when
heating stops.

GA (gas or oil heating): The fan starts when the temperature inside the
plenum rises above the Fan Limit (see item 11) and stops when the tem-
perature drops 12°C below the Fan Limit. Note: The fan will not start if
the plenum temperature sensor is not connected to the controller
.

11

Fan limit

38 to 90°C

(100 to 194°F)

80°C

(176°F)

This parameter is available only when gas heating is selected (see item 10).

WARNING: FLMT can be used in parallel with an UL353-approved
device but they do not replace such device.

NOTE: The fan will not start if you raise FLMT above its maximum (--).

12

Smart Fan

On / OF

OF

On: Smart Fan is On (see section 4.7).

OF: Smart Fan is Off.

13

Temperature setback

0 to 9°C

(0 to 16°F)

0°C

(0°F)

Set the amount of temperature setback when the controller is placed in
Unoccupied mode (see section 5.6).

14

Outdoor temperature

display

On / OF

On

Select between displaying the outdoor temperature or the indoor humidity
level.

On: Displays the outdoor temperature.

OF: Displays the indoor humidity level.

NOTE: To display the outdoor temperature, the outdoor sensor must be
connected.

15

Humidifier

operating mode

Co / HE / Fn

HE

Co (conventional): The humidifier will operate if the humidity is too low. If
the fan is not already On, it will turn On at the same time as the humidi-
fier.

HE (heat): The humidifier can operate only when heating is activated.

Fn (fan): The humidifier can operate as long as the fan is running,
whether heating is activated or not.

NOTE: The humidifier is disabled when cooling is activated.

16

Automatic humidity

adjustment

On / OF

OF

Allows you to set the humidity control to automatic mode.

On (automatic): The humidity level is automatically regulated by the con-
troller according to the outdoor temperature to avoid condensation or ice
formation on windows while providing enough humidity for your comfort
(see item 17).

OF (manual): The user manually sets the humidity level (see item 17).

17**

Humidity setpoint

5 to 60%

5 %

Set the desired humidity level. This parameter is available only when the
humidity control is placed in manual mode (see item 16).

Humidity offset

-9 to 9%

0

This parameter is available only when the humidity control is placed in auto-
matic mode (see item 16). It allows the user to apply an offset to the auto-
matic humidity control. For example, the user can enter a negative offset if
there is ice formation or condensation on the windows.

*

Parameters 2 to 6 are not available when the controller is configured for 1H1C, 2H2C or 3H3C heat pump.

**

Only parameter 17 is available when the controller is in user mode (SW1-2 switch).