Alliance Laundry Systems HD110 User Manual

Page 26

Advertising
background image

Page 23

For Exhaust Duct more than 14 feet (5 m) and 2 elbows equivalent
and more than 0.3 inches (8 mm) static pressure.

1. Make-up air from outside building may enter enclosure from

top or side walls. (See Dryer Make-Up Air Requirements
Chart)

2. Use constant diameter duct with area equal to the sum of dryer

duct areas.

EXAMPLE: 6-8 in. (153-204 mm) diameter duct = 1-19.6 in.
(26-498 mm) diameter duct in area. Use 20 in. (508 mm)
diameter duct or diameter to match tube-axial fan.

3. Enclosure (plenum) with service door. This separates the

dryer air from room comfort air. If dryers use room air instead
of outside air, the heat loss can be another 25 Btu/h

(6.3 kcal/h) for each cubic foot per minute (cfm) used.

EXAMPLE: 110 lb. dryer, 2000 cfm (3400 m

3

/h) =

50,000 Btu/h (12,600 kcal/h) loss.

4. Zero inches clearance to combustible material allowed on

sides and at points within 4 inches (102 mm) of front on top.

5. Heat loss into laundry room from dryer fronts only is about

60 Btu/h (16 kcal/h) per square foot.

6. Flange mounted, belt driven tube-axial fan. Fan must run when

one or more dryers are running. See suggested Automatic
Electrical Control Wiring Diagram on page 23.
Must meet
local electrical codes. Fan air flow (cfm) is equal to sum of
dryer air flows, but static pressure (SP) is dependent on length
of pipe and number of elbows.

7. Barometric bypass damper—Adjust to closed flutter position

with all dryers and exhaust fan running. Must be located within
enclosure.

CAUTION
Never
install hot water heaters or other gas appliances in the
same room as dryers. Never
install cooling exhaust fans in the
same room as dryers.

CAUTION
Never exhaust dryers with other types of equipment.

DRYER INSTALLATION WITH MULTIPLE EXHAUST

EXHAUST
INSTALLATION—
MULTIPLE MANIFOLD
DUCT

Advertising
This manual is related to the following products: