Notified applications screen – HP UPS Network Module User Manual

Page 42

Advertising
background image

HP UPS Network Module web interface 42

Notified Applications screen

Click Notified Applications in the menu tree to display the Notified Applications screen. This screen allows an

administrator to manage trap receivers and HPPP Clients installed on protected servers. You can add trap

receivers using this screen, but all HPPP Clients are configured at the servers, and are automatically added
by the UPS Network Module.

NOTE:

To query SNMP data, you do not need to add SNMP Manager.

The following information is available on the Notified Applications screen:

Nr—The assigned application number in the Notified Applications list

Hostname or IP Address—The host name or IP address of the server running the application
The host name of the computer displays when the IP address can be converted into a host name by a
DNS server, or if the application has been entered using the server host name.

Application Name—The name assigned to the application on the Trap Receivers Settings screen (on
page

44

)

Applications appear in the order in which they subscribe to the UPS Network Module. SNMP
management applications, such as HP Systems Insight Manager, can receive notifications from the UPS

Network Module.

Output—The name of the UPS load segment from which the Client is powered

Shutdown after (min)—The time available to the user after a utility power failure occurs and before the
UPS shutdown sequence initiates
This value is configured in the HPPP Client and displays in this column.

OS Shutdown time (sec)—The time required to completely shut down the operating system
This value is configured in the HPPP Client and displays in this column.

Link—A hyperlinked icon to the web interface for the notified application

(

HTTP Connection,

HTTPS Connection, or

Communication Loss)