Output tolerance specifications, Output feature specifications, Battery specifications – HP UPS Extended Runtime Module User Manual

Page 48: Battery runtime, Battery specifications battery runtime

Advertising
background image

Specifications 48

Configuration setting (VAC)

Available nominal output voltage (VAC)

208

208

230

230

240

240

Output tolerance specifications

Source of power

Regulation

Utility power (nominal
range)

-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer
Business Equipment Manufacturers
Association)

Battery power

±5% of nominal output voltage rating

Output feature specifications

Feature

Specification

Online efficiency

94% nominal input voltage

Voltage wave shape

Sine wave; 5% THD with typical PFC load

Surge suppression

High-energy 6500 A peak

Noise filtering

MOVs and line filter for normal and common mode
use

Battery specifications

Feature

Specification

Type

12 V, 5 AH, sealed, maintenance-free, rechargeable, valve
regulated lead-acid batteries with a 3-5 year service life at
25°C (77°F).

Voltage

The battery modules have a battery string voltage of 120 V.

Charging

Complete charge takes no more than 24 hours. After
approximately 4 hours, the batteries reach 90% charge at
default nominal utility voltage and no load.

Battery runtime

Load, percent

Estimated battery
runtime

Runtime with one ERM

Runtime with two ERMs

20

40 minutes

120 minutes

250 minutes

50

12 minutes

45 minutes

100 minutes

80

6.5 minutes

30 minutes

60 minutes

100

5 minutes

20 minutes

40 minutes