Hp 750 w dc cs he power supply (94% efficiency) – HP ProLiant DL160 Gen8 Server User Manual

Page 93

Advertising
background image

Specifications 93

Rated input frequency

50 Hz to 60 Hz

Rated input current

9 A to 4.5 A

Rated input power

831 W at 115V AC input

808 W at 230V AC input

Btus per hour

2878 at 100 V AC
2834 at 115 V AC

2769 at 200 V AC

2758 at 230 V AC

Power supply output

Rated steady-state power

750 W at 100 V to 120 V AC

input

750 W at 200 V to 240 V AC
input

Maximum peak power

750 W at 100 V to 120 V AC

input

750 W at 200 V to 240 V AC
input

HP 750 W DC CS HE power supply (94% efficiency)

Specification

Value

Input requirements

Rated input voltage

-36 V DC to -72 V DC
-48 V DC nominal input

Rated input current

23 A at -36 V DC input

17 A at -48 V DC input, nominal

input
11 A at -72 V DC input

Rated input power (W)

815 W at -36 V DC input

805 W at -48 V DC input, nominal

input
795 W at -72 V DC input

Rated input power (Btus per
hour)

2780 at -36 V DC input

2740 at -48 V DC input, nominal

input
2720 at -72 V DC input

Power supply output

Rated steady-state power (W) 750 W
Maximum peak power (W)

750 W

CAUTION:

This equipment is designed to permit the connection of the earthed conductor of the

DC supply circuit to the earthing conductor at the equipment.

If this connection is made, all of the following must be met:

This equipment must be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply

system earthing electrode conductor is connected.

This equipment must be located in the same immediate area (such as adjacent cabinets) as any

other equipment that has a connection between the earthed conductor of the same DC supply
circuit and the earthing conductor, and also the point of earthing of the DC system. The DC