AMX Energy Management Modules RDM-3EM User Manual

Rdm-3em and rdm-6em, Installation sheet, Energy management modules

Advertising
background image

Installation Sheet

RDM-3EM and RDM-6EM

Energy Management Modules

The RDM-3EM (FG606-81) and RDM-6EM (FG606-80) are 3 and 6
channel switching energy management modules. They are designed for use
with the RDA series of enclosures in an AMX Lighting™ system.
For more detailed installation and operating instructions, refer to the Radia
Lighting Control System
Instruction Manual, available on-line at
www.amx.com.
The RDM-3EM and RDM-6EM are designed with the most advanced
latching energy management relays to support heavy duty commercial
applications, building automation, and loadside management. Equipped
with on-board module microprocessors, both support relay control and
sequencing. Features include:

User selectable delays in sequencing mode to minimize inrush current

and stress on the electrical distribution system.

Selectable strapping facilitates multiple relays on one Radia control

channel for large area control.

Manual on/off override on each relay independent of control system.

Relays retain their state during power and control system outages.

Visual Status Indicators on each relay.

Latching relays do not consume any control current, except when they

change state, eliminating the need for additional Radia power supplies.

Specifications

Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)

Non-phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 4.4 in lbs.

Wire size: 26 AWG to 10 AWG

Wire stripping length: 0.28" (7 mm)

Weight: 15 oz. (RDM-3EM) and 1.5 lbs. (RDM-6EM)

Included Accessories

4 mounting screws

Control wiring harness

RDM-3EM and RDM-6EM UL and C-Ul Ratings

General purpose: 120, 240, 277, and 347

*

VAC, 20 A

UL/CUL916 Energy Management Systems.

UL/CUL508 Industrial Control Systems.

Suggested Switched Loads

Incandescent

Fluorescent

Transformer

Low voltage

General purpose

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Test loads for shorts before connecting.

Use low voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

For indoor use only.

FIG. 1

RDM-6EM

Mounting
points

Relays

Sequencing
Delay Jumpers
(JP1 and JP2)

Control
Port
Strapping
Jumpers
(JP3 - JP7)

(1-6)

1

2

3

4

5

6

Mounting points

FIG. 2

RDM-3EM

Mounting
points

Relays

Sequencing
Delay Jumpers
(JP1 and JP2)

Control
Port
Strapping
Jumpers
(JP3 - JP4)

(1-3)

1

2

3

Mounting points

*

Agency approval pending

Advertising
This manual is related to the following products: