CMP PX2KX-REX User Manual

Cable gland types

Advertising
background image

INSTALLATION INSTRUCTIONS FOR

CMP CABLE GLAND TYPES PX2K-REX,

PX2KW-REX, & PX2KX-REX

FOR TERMINATION OF CABLES WITH WIRE BRAID, TAPE ARMOUR (STA/DSTA), STRIP ARMOUR &

SINGLE WIRE ARMOUR (SWA) (WITH LEAD INNER SHEATH ON PB VARIANTS) . FOR USE IN

HAZARDOUS LOCATIONS.

INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC

CM

P

Do

cu

m

en

tN

o.

FI

40

2

Is

su

e

5

01

13

0518

Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS

Tel: +44 191 265 7411 • Fax: +44 191 265 0581

E-Mail: [email protected] • Web: www.cmp-products.com

Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.

I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the following

standards:-

EN60079-0:2006, EN60079-1:2007, EN60079-7:2007, EN60079-15:2005, BS 6121:1989, EN50262:1998 (Amd 2001), EN61241-0:2004, EN61241-1:2004

Dr Geof Mood - Technical Director - (Authorised Person)

DUBAI

• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH

www.cmp-products.com

Ca

bl

e

Gl

an

d

Se

le

ct

io

n

Ta

bl

e

Logo’s shown for illustration purposes only. Please check certification for details

Cable

Gland

Size

Available Entry

Threads

Minimu

m

Thread

Length

Number

Of

Cores

Diameter

Over

Conductors

Maximum

Diameter

Over Lead

Sheath

Overall Cable

Diameter

Armour Wire Diameter

Across

Flats

Across

Corners

Ordering

Reference

(Brass Metric)

**

Standard

Option

Grooved Cone Stepped Cone

Metric

NPT

NPT

Max

Max

Min

Max

Min

Max

Min

Max

Max

Max

20S/16

M20

1/2”

3/4”

15.0

11

12.6

14.9

6.1

11.5

0.15

0.5

0.8

1.0

30.5

33.6

20S16PX2KREX1RA

20S

M20

1/2”

3/4”

15.0

11

12.6

14.9

9.5

15.9

0.15

0.5

0.8

1.25

30.5

33.6

20SPX2KREX1RA

20

M20

1/2”

3/4”

15.0

21

12.6

19.9

12.5

20.9

0.2

0.5

0.8

1.25

30.5

33.6

20PX2KREX1RA

25S

M25

3/4”

1”

15.0

38

17.5

21.0

14.0

22.0

0.2

0.6

1.25

1.6

37.5

41.3

25SPX2KREX1RA

25

M25

3/4”

1”

15.0

38

17.5

25.2

18.2

26.2

0.2

0.6

1.25

1.6

27.5

41.3

25PX2KREX1RA

32

M32

1”

1-1/4”

15.0

59

23.6

32.9

23.7

37.9

0.2

0.6

1.6

2.0

55.0

50.6

32PX2KREX1RA

40

M40

1-1/4”

1-1/2”

15.0

89

30.0

39.4

27.9

40.4

0.2

0.8

1.6

2.0

55.0

60.5

40PX2KREX1RA

50S

M50

1-1/2”

2”

15.0

115

36.6

45.7

35.2

46.7

0.2

0.8

2.0

2.5

60.0

66.0

50SPX2KREX1RA

50

M50

2”

2-1/2”

15.0

115

41.0

52.1

40.4

53.1

0.3

0.8

2.0

2.5

70.0

77.0

50PX2KREX1RA

63S

M63

2”

2-1/2”

15.0

140

47.9

58.4

45.5

59.4

0.3

0.8

2.0

2.5

75.0

82.5

63SPX2KREX1RA

63

M63

2-1/2”

3”

15.0

140

53.7

64.9

54.6

65.9

0.3

0.8

2.0

2.5

80.0

88.0

63PX2KREX1RA

75S

M75

2-1/2”

3”

15.0

140

59.9

72.8

58.0

72.1

0.3

0.8

2.0

2.5

89.0

97.9

75SPX2KREX1RA

75

M75

3”

3-1/2”

15.0

140

64.3

77.5

66.7

78.5

0.3

0.8

2.5

3.0

99.0

108.9

75PX2KREX1RA

90

M90

3-1/2”

3-1/2””

15.0

140

75.3

89.4

78.2

90.4

0.4

0.8

3.0

3.5

114.0

125.4

90PX2KREX1RA

100

M100

4”

-

15.0

200

85.6

100.5

86.1

101.5

0.4

0.8

3.15

4.0

133.0

146.3

100PX2KREX1RA

All dimensions in millimetres unless otherwise stated

Note:

Codes shown are for PX2K-REX glands, for PX2KW-REX or PX2KX-REX add “W” or “X” respectively, e.g. 20PX2KWREX1RA, 20PX2KXREX1RA

CABLE GLAND TYPES

CABLE GLAND TYPES

PX2K-REX, PX2KW-REX &

PX2K-REX, PX2KW-REX &

PX2KX-REX & VARIANTS

PX2KX-REX & VARIANTS

TECHNICAL DATA

CABLE GLAND TYPE

: PX2K-REX, PX2KW-REX & PX2KX-REX

INGRESS PROTECTION

: IP66, IP67, IP68, Type 4X; Oil Resistant II

PROCESS CONTROL SYSTEM

: BS EN ISO 9001

: ISO / IEC 80079-34:2011

HAZARDOUS AREA CLASSIFICATION

ATEX CERTIFICATION No

: SIRA 06ATEX1097X & SIRA 07ATEX4326X

ATEX CERTIFICATION CODE

:

II 2 GD Ex d IIC / Ex e II / Ex nR II / Ex tD A21 IP66

IEC Ex CERTIFICATION No

: IEC Ex SIR.06.0044X

IEC Ex CERTIFICATION CODE

: Ex d IIC / Ex e IIC / Ex nR II / Ex tD A21 IP66

CSA-US CERTIFICATION No.

: 2288626

CSA-US CERTIFICATION CODE

: Class I Div 1, 2, Groups A, B, C, D: Class II, Div 1, 2, Groups F and G; Class III, Div 1, 2;

Class I Zone 1 AEx d IIC / AEx e II

(Code details depends upon application - please see certificate)

INSTALLATION INSTRUCTIONS

Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions

before beginning installation.

SPECIAL CONDITIONS FOR SAFE USE

1. The cable gland ranges shall only be used where the temperature, at the point of entry, is in the following ranges:

-60°C to +85°C.

2. The cable glands used for terminating braid cable are only suitable for fixed installations. Cables must be effectively clamped to prevent twisting

and pulling.

3. The entry component threads may need additional sealing to maintain the ingress protection ratings as applicable to the associated equipment to

which it is attached.

4. According to the CEC wiring code, connectors with metric threads are only suitable for Areas Classified in ZONES unless fitted with an approved

Metric to NPT thread conversion adaptor.

5. Wiring method for type of cables that can be used in Class I, Div. 1, 2, and Class I, Zone 1, 2, Classified Areas according to 60079-14 installation

wiring method restrictions.

6. Shipboard Cables are for use on Marine Platform or shipboards only and are subject to local authorities having jurisdiction on the installation.

ACCESSORIES

The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-

Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud *

Advertising
This manual is related to the following products: