INSTALLATION INSTRUCTIONS FOR CMP CABLE CONNECTOR TYPE TMC2

DUBAI

• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH

DUBAI

• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH

www.cmp-products.com

www.cmp-products.com

CABLE CONNECTOR COMPONENTS

PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION

1. Cable preparation.

Strip back the jacket and armor to suit the equipment geometry.

2. Using the armor measure guide, expose the armor by stripping back the cable jacket by distance “L”.

3. Screw the connector into the equipment, or if it is fitted into a clearance hole, secure with a

locknut.

Loosen the outer nut to ensure that the Grounding Spring (4) and the Jacket Seal (6) are in a

relaxed state. IT IS NOT NECESSARY TO SEPERATE THE CONNECTOR COMPONENTS.

4. Pass the cable through the connector until the armor makes contact with the end stop.

If it is not possible for the conductors to pass through the end stop then it should be removed so

that the armor can make contact with the integral end stop within the entry component.

5. Finally, tighten the Outer Nut (7) to compress the Grounding Spring (4) to secure the armor, and

also to cpmpress the Jacket Seal (6) onto the cable jacket. Do not over-tighten. The Entry

Component (2) and the Outer Nut (7) do not have to close face to face.

THIS COMPLETES THE TERMINATION

2

3

1

1. Face Seal

2. Entry Component

3. End Stop

4. Grounding Spring

5. Angled Spacer

6. Jacket Seal

7. Outer Nut

4

5

6

7

Armor Measure

Guide

L

L

L = Distance from

groove to rear of nut.

End Stop