f. Troubleshooting Flow Chart - Quick Reference...

Third Visual Check

(Does Main Burner Ignite?)

Does

main burner

remain

lit?

Does

the Flame Probe

have carbon or

dust build

up?

Reposition Flame Sensor Probe to achieve a
2µa or greater sensor current or, if
unattainable, replace the Sensor Probe
Assembly.

Correct

ground wiring

Control's heat requirements

satisfied.
DSI cycle is complete.

Replace Flame Sensor

Assembly.
Energize system and check
for proper operation.

De-energize

the system and disconnect

Flame Sensor from the

DSI Module. Connect an ohmmeter

across the Flame Sensor

Sensor and ground.

Is resistance less

than 50 mega-ohms?

Does

ignitor spark turn

"OFF" with main

burner flame still

present?

Does ignitor spark continue
with burner flame present?

Remove Flame Sensor

Assembly.
Clean the surface of the
Flame Sensor Rod with
fine steel wool or emery
cloth, then reinstall.
Energize system and
check for proper operation.

Yes

Yes

Connect

ohmmeter across

Flame Sensor lead

terminal and Flame Sensor.

Does continuity

exist?

Is

DSI Module "GND"

terminal properly

connected to

ground?

Is

Flame Sensor Probe

properly located in the flame?

Proper flame location would

provide adequate flame current

yet will not exceed maximum rod

temperature. Microammeter

reads 2µa or

greater.

Replace

DSI Module