Specifications

46

900-0114-01-00 Rev A

Environmental Specifications

Table 15 Environmental Specifications for All Models

Specification Value

Rated Temperature Range (meets all specifications)

32 °F to 122 °F
(0 °C to 50 °C)

Operational Temperature Range (functions, but does not necessarily meet all specifications)

–40 °F to 140 °F
(–40 °C to 60 °C)

Storage Temperature Range

–40 °F to 140 °F
(–40 °C to 60 °C)

Grid-Interactive Use

Inverters intended for grid-interactive use must comply with established standards which provide
regulation for acceptable output voltage ranges, acceptable output frequency, total harmonic
distortion (THD) and anti-islanding performance when the inverter is exporting power to a
utility source.

The OutBack grid-interactive models are validated through compliance testing. The following
specifications refer to exporting power to a simulated utility source of less than 1% voltage total
harmonic distortion (THD).

 The THD of the root mean square (RMS) current is less than 5%.
 The output of the GFX inverter exceeds the minimum power factor of 0.85 with a typical power factor of

0.96 or better.

 All GFX Series inverters are tested to comply with Table 16.

Table 16 Interconnection Response to Voltage and Frequency

Voltage Range

(AC Volts)

Frequency (Hz)

Allowed Time

(Seconds)

Measured Time

(Seconds)

V < 60

60

0.16

0.020

60 ≤ V < 105.6

60

2.00

0.155

105.6 to 132

60

No interruption

No interruption

132 < V < 144

60

1.00

0.157

V ≥ 144

60

0.16

Instantaneous, but 0.137 seconds

to zero current

IEEE setting

> 60.5

0.16

0.098

IEEE setting

< 59.3

0.16

0.102

User setting

> 62

1.00

0.605

User setting

< 58

1.00

0.656

The acceptance ranges are selected using the system display. The options are IEEE and USER. The
default setting is USER.

 The IEEE option allows a range of 105.6 – 132 Vac at 59.3 – 60.5 Hz.
 The USER option is not a fixed setting. It follows the ac1/grid lower limit and ac1/grid upper limit settings

as shown on the tables beginning on page 47. The default is a range of 108 – 132 Vac at 58 – 62 Hz.

Reconnection delay is 12 seconds after restoration of acceptable conditions. Sell delay is one minute.
These settings are not adjustable.