Offset, E 36, 35 f – Outback Power Systems GS3548E Operators Manual User Manual

Page 37: Operation

Advertising
background image

Operation

900-0145-01-01 Rev A

35

Offset

This operation is designed to use excess battery energy to power the loads when an AC source is
present. This allows the system to take advantage of renewable energy sources, in effect “offsetting”

dependence on the AC source.
A renewable energy source will raise the battery voltage as it charges the batteries. When the voltage

exceeds a designated reference voltage, the Radian inverter begins drawing power from the batteries

(discharging them) and using that power to offset usage of the AC source. The batteries are kept at

equilibrium and are maintained at the reference voltage.
The Radian inverter uses excess DC energy for offset under the following rules:

If the load demand is higher than the exported power, the inverter’s use of the AC source is reduced. The
exported amount of power has “offset” the same amount of demand on the AC source. (This is sometimes
known as “selling to the loads”.)

If the excess DC energy (and exported power) is equal or greater than the load demand, and the Radian is in
the

Grid Tied input mode, the inverter will sell the additional power to the utility grid. This is the key priority

of the

Grid Tied mode.

The Radian inverter uses several set points as reference voltages for the Offset operation, particularly
the battery charger settings.

The charger settings

Absorb Voltage, Float Voltage, and Equalize Voltage (as shown in the system display)

are all used as reference voltages. Normally the charger regulates to these set points by adding power to
the batteries. Offsetting does the opposite; it uses the same set points but regulates the voltage by
removing power from the batteries.

If none of the battery charger’s timers are active, the Offset voltage is

Sell Voltage in the Grid-Tie Sell menu.

This is true in any input mode where Offset is used, not just the

Grid Tied input mode.

The

Grid Zero mode only uses a single reference voltage for Offset, the DoD Volts setting.

NOTES:

Offset operation is not available in the Generator, UPS, and Backup input modes.

Offset operation is available in the Support, Grid Tied, and Grid Zero modes.

Offset operation is available in the Mini Grid mode. However, it may not be used often since the Mini Grid

priority is to avoid grid use.

The Grid-Tie Enable menu item must be set to Y (yes) for Offset to work. This is true even if the inverter is

not used in a grid-tied mode or application.

Table 3

Offset Interaction with AC Source

Mode

Excess DC ≥ loads

Excess DC < loads

Generator

N/A; Offset operation does not function

Support

Offsets load use, but also uses DC and batteries to support the AC source based on

Support mode settings

Grid Tied

Sells excess to AC source (grid); remains connected

Offsets load use with whatever power is available

UPS

N/A; Offset operation does not function

Backup

N/A; Offset operation does not function

Mini Grid

Offsets load use with whatever power is available; inapplicable if disconnected from utility grid

Grid Zero

Offsets load use, but only according to the

DoD Volts setting

Advertising
This manual is related to the following products: