Table 6

Troubleshooting

Symptom

Possible Cause

Possible Remedy

Advanced

Generator Start

(

AGS) fails to

activate when

conditions are met

(or starts when

conditions are not

met).

MATE3 system display only:

AGS

function does not work if

another valid input is present.

Check both inputs for a second AC source (utility grid). If the
inverter detects an acceptable AC source, it will not allow

AGS.

This is true even if it is internally disconnected from the source
(due to

HBX mode, Mini Grid mode, or similar programming).

MATE3 system display is not

present.

AGS programming is located in the MATE3 and cannot function if
the MATE3 is removed.

Other AUX functions are in

operation.

Gen Alert or another AUX function may try to start or stop the
generator using the wrong criteria. Make sure all other AUX

functions are disabled.

AGS or Gen Alert
functions start the

generator, but the

inverter does not

accept the power

and shuts off the

generator again.

The inverter’s

GRID input is in

use and the input priority is set

to

GRID.

If the input priority is set to

GRID and the

GRID terminals are

energized, an automatically controlled generator will shut down.
This could indicate that the generator has been wired to the

GRID

input, or it could indicate that another AC source is active on
the

GRID input while the generator is using the GEN input.

The

GEN input must be the only terminals in use when

automatically controlling a generator.
Either the

GRID or GEN input can be used when manually

controlling a generator.

Module Select

The GS7048E uses two high-frequency H-Bridge FET modules. The dual design allows half the inverter

to shut down for lower idle consumption. Normally this is automatically selected. If one module fails

or if troubleshooting is otherwise needed, the module selection can be performed manually. The

GS7048E can be directed to use a single, specified module (left or right), or it can be directed to turn

on both modules continuously. This procedure should only be performed if directed by OutBack
Technical Support (see inside the front cover of this manual).
Although the GS3548E has only a single module, this command is still available. The default setting is

Left, which is the location of the module. Do not change this setting in the GS3548E.
The Module Select menu options are displayed as part of Table 16, which begins on page 67.