Two-wire-start (12v aux terminals), Installation – Outback Power Systems GS3548E Installation Manual User Manual

Page 29

Advertising
background image

Installation

900-0144-01-01 Rev A

27

In other cases, or in the case of a three-wire-start generator, the inverter should use the

12V AUX

terminals instead, in conjunction with a three-to-two wire converter. (See pages 27 and 28.)

Figure 23 Two-Wire Generator Start (RELAY AUX)

Two-Wire-Start (12V AUX Terminals)

The 12 Vdc signal provided by the

12V AUX terminals can be switched on and off to provide a start

signal. It is not usually recommended to connect the

AUX terminals directly to the generator, but to

use the

12V AUX terminals to energize the coil of a 12 Vdc automotive or similar relay.

The OutBack FLEXware Relay Assembly depicted in Figure 24 is sold for this purpose. The relay

contacts can serve in place of the generator’s start switch. The battery shown in Figure 24 is shown for

clarity. Usually it is part of the generator’s internal starting circuit and is not an external component.
The drawing below is one example of a possible arrangement. Specific arrangements, relays, and

other elements depend on the requirements of the installation and of the generator.

Figure 24 Two-Wire Generator Start (12V AUX)

RELAY AUX

Terminals

Starting

Switch

Two-Wire-Start

Generator

Starting

Terminals

Generator

Battery

Relay

Contacts

Relay

Coil

Two-Wire-Start

Generator

1

1

12V AUX Terminals

Advertising
This manual is related to the following products: