Outback Power Systems FLEXmax Extreme Quick Start Guide User Manual

Aflexmax extreme, Charge controller, Battery bank

Advertising
background image

900-0151-01-00 Rev A.vsd\Install\2013-05-31

©2013 OutBack Power Technologies. All Rights Reserved.

WARNING: Burn Hazard

The heat sink can become hot when the charge controller is operating.
Use caution when touching it during operation.

Dimensions

Height: 18.8" (47.1 cm); with fan 22.06" (56.0 cm)
Width: 8.8" (22.4 cm)
Depth to Wall: 6.0" (15.2 cm)

Mounting

The FLEXmax Extreme must be mounted upright at least 36" (91.4 cm)
above the ground or floor. Installation in shade is recommended.
Conduit hubs must be connected to the conduit before connecting to
the FLEXmax Extreme.
Clearance requirements are a minimum of 6“ (15.2 cm) above and
below the controller.
The unit can be mounted using either brackets (see A) or keyhole slots
(see B) on a secure mounting surface.

Name Color

Pattern

Bulk Abs Float EQ

Other

Off

Off

< 10 W PV available

Battery rest

Blue Solid

X

X

Blue

Flash long

X

Blue

Flash short

X

Float

Amber

Solid

X

X

≥ 1.91 Vpc

Green

Solid

X

Red

Solid

X

X

Battery discharge

<1.91 Vpc

Red

Flash

X

X

Critical batt discharge <1.75 Vpc

Amber/ Green

Flash

X

≤ EQ

Amber/ Red

Flash

X

Critical batt discharge <1.75 Vpc

AUX

Yellow

Solid

AUX active

Fault

Red

Solid

External Fault

N/A

Status

Any

N/A

LED Indicators (see wiring section)

Indicator

Controller State

Voltage

Charge

Included in Package

FM Extreme-150VDC
2 x Mounting Bracket
Silicone Grease Package
2 x Ferrite Clamp (install
on HUB/DEVICE and
RTS ports)

Provided by Customer

PV Array
Batteries
MATE3
Fan Kit
Disconnect Devices
Ground Fault Protection
Wiring & Cabling

Temperature

Range of ambient operating
temperature: -20°C to 45°C
(-4°F to 113°F)
Unit output derated above 45°C
(113°F)

A

FLEXmax Extreme

Charge Controller

PV Combiner

Photovoltaic Array (PV)

Ground

Bus

Battery Bank

ON

OFF

BAT+

BAT–

PV–

PV+

Battery

Disconnect

(external)

Ground Fault Protection

(not provided, required by Article 690 of NEC)

Negative

Bus

ON

OFF

PV

Disconnect

(external)

Tighten all wire lugs and
ground terminals to 4 Nm
(35 in-lb) torque.
Use copper wiring only
(rated 90°C or higher).
Refer to the NEC and other
electrical codes for PV array
cable sizing, length, and
ampacity.
Use #4 AWG (25 mm

2

)

(minimum) for the controller
output terminals to the
batteries; output can accept
up to #2 AWG (35 mm

2

).

Negative-ground installation is
depicted here; positive
grounding is also permitted.

IMPORTANT: Example only.

Actual wiring may vary. All
configurations must comply with
local and national electric codes.
Consult your local electric authority
to ensure compliance.

Negative

Positive

Ground

DC LEGEND

IMPORTANT:

Wire sizes must
comply with local and
national codes. To
comply with the NEC,
input conductors and
circuit breakers must
be rated at 1.56 times
the short-circuit current
of the PV array.

OFF

O

O

F

F

O

FAULT

PV

INACTIVE

NORMAL

PV ACTIVE

PV ARRAY

GROUND FAULT

DETECTOR

INTERRUPTER

B

¼” hex head
lag screws

Keyhole Slots

(#14 slotted wood screws)

Securing Holes

(¼” hex head lag screws)

LED Indicators

(see above)

LED Indicators

Charging (Blue)

Status (Green/Red or Amber)

Auxiliary

Fault

NOTE: Overcurrent protection

for the battery circuit is to be
provided by installer.

Battery Nominal Voltages:

12-volt, 24-volt, 36-volt,48-volt, 60-volt

1

4

2

3