MAINTENANCE INSTRUCTIONS

COMBINATION AIR VALVE

BARAK, MODEL DG-10 1”

GENERAL INSTRUCTIONS

Routine service is an integral part of the standard

procedure for maintenance of a water supply system.

Recommended routine maintenance– once or twice a year, according to the quality and

type of the fluids in the system.

PROCEDURE

Close the service valve under the valve base before servicing.

Turn the valve body (1) counterclockwise, release and remove.

From inside the valve body (1), remove the clamping stem (4) and carefully pull out

the float (5) with the attached rolling seal (3).

Check the soundness of the rolling seal (3) by washing it with water and examining

it. Replace the rolling seal in case it is torn.

Wash the body (1) and the float (5) with clean water and examine it for damage.

Replace the float (5) if it is damaged.

Clean the drainage elbow (2) to remove insects and debris.

Return the float (5) with the attached rolling seal (3) to its original position in the

valve body (1) and lock them into place with the clamping stem (4).

Return the valve body (1) to the base (7) and close by turning it clockwise, making

sure that the O-ring (6) is situated in its place in the base of the valve (7).

Remember to open the service valve after the servicing.

PARTS SPECIFICATION

NO.

DESCRIPTION

MATERIAL

1.

Body

Reinforced Nylon

2.

Drainage Elbow

Polypropylene

3.

Rolling Seal

E.P.D.M.

4.

Clamping Stem

Reinforced Nylon

5.

Float

Foamed Polypropylene

6.

O-ring

Buna-n

7.

Base

Reinforced Nylon / Brass