N-030

Symptom

Cause

Corrective action

1

The seats no properly sealed

(reverse flow occurring)

1) Hard solid stuck on the seats
2) Elastomer deterioration.

3) Exaggerated clearance

between the internal parts due
to Erosion

1) Dismantle the N-030 from

the line and clean both the
two seats surfaces.

2) As above and change the

elastomer seal.

3) Change the complete disc

and arm assembly

2

Leakage from the shaft O-

Ring

1) O-ring Elastomer

deterioration.

2) Shaft Erosion at O-rings

contact

1) Change the O-rings plugs.

2) Replace the complete

shaft.

3

Leakage between the body

and the plugs

The fiber seal broken.

Replace the fiver seal.