B. Periodic Maintenance

1. Greasing of the bolt and key of the counter weight.
2. Greasing the bolts of the valve’s cover (lid) .
3. Brush painting of the surface area of the valve body.
4. In case the valve is installed in waste water system , open the valve’s

cover and wash the internal part from dirt, solids and debris


Symptom

Cause

Corrective action

1 Leakage from the

shaft O-Ring

1) O-ring Elastomer
deterioration.
2) Shaft Erosion at
O-rings contact

1) Change the

O-rings plugs.

2) Replace the complete

shaft.

2 The

seats

no

properly sealed
(reverse flow
occurring)

1)Hard solid stuck on the
seats


2) Elastomer deterioration.

3) Exaggerated clearance
between the internal parts
due to Erosion

1) Open the upper lid and

clean both the two
seats. If needed,
replace the body seat.

2) Replace the rubber-

lined disc.

3) Change the complete

disc and arm assembly

3 The

micro

switch

is out of function

The micro switch roller is
no more in contact with the
actuator came

Check the tightening of
the came retaining bolt on
the shaft. Carefully fix the
came in the right position
for correct indication.

4 Leakage from the

upper cover

Defective O-ring seal

Change the lid O-ring
seal