MAINTENANCE INSTRUCTIONS

5

4

3

2

1

6

7

COMBINATION AIR VALVE

BARAK, MODEL D-040 2”

GENERAL INSTRUCTIONS

- Routine service is an integral part of the standard procedure for maintenance of a

water supply system.

- Recommended routine maintenance– once or twice a year, according to the

quality and type of the fluids in the system.

PROCEDURE

1. Close the service valve under the valve base before servicing.

2. Turn the valve body (1) counterclockwise, release and remove.

3. Remove the clamping stem (4) from inside the valve body (1) and carefully

pull out the float (5) with the attached rolling seal (3).

4. Check the soundness of the rolling seal (3) by washing it with water and

examining it. Note: Replace the rolling seal (3) in case it is torn.

5. Wash the body (1) and the float (5) with clean water and examine for damage.

Note: Replace the float (5) if it is damaged.

6. Clean the drainage elbow (2) to remove insects and debris.

7. Return the float (5) with the attached rolling seal (3) to its original position in

the valve body (1) and lock them into place with the clamping stem (4).

8. Return the valve body (1) to the base (7) and close by turning it clockwise.

Note: First make sure the O-ring (6) is seated properly in the base of the valve (7).

9. Remember to open the service valve after the servicing.

PARTS SPECIFICATION

NO.

DESCRIPTION

MATERIAL

1.

Body

Reinforced Nylon

2.

Drainage Elbow

Polypropylene

3.

Rolling Seal Assembly

4.

Clamping Stem

Reinforced Nylon

5.

Float

Foamed Polypropylene

6.

O-Ring

BUNA-N

7.

Base

Reinforced Nylon / Brass