State Standard Systems User Manual

Page 34

Advertising
background image

34

proBlem

checK this

possiBle cause

corrective action

Pump does not start

Electrical power supply

Controller plug disconnected

Reconnect control plug to

power outlet

Blown fuse or breaker tripped

on overload

Determine cause and replace

fuse or reset breaker

Pump

Motor failure

Replace pump

Sensors

Defective sensors, sensor

error

Check wiring continuity.

Repair or replace

Pump starts, but cycles

continuously

Differential controller

On and/or off temperature

differential set points too low

Reset on and off

differentials according to

recommendations

Piping

Reversed connections to

collectors

Compare with system

schematic and reconnect

properly

Sensors

Improper location

Compare with system

schematic and reconnect

properly

Pump cycles after dark

Differential controller

Recooling function active

and max temperature setting

exceeded

Controller operating properly.

No fault.

Sensors

Defective sensors, sensor

error

Check wiring continuity.

Repair or replace

Pump runs continuously

Differential controller

Off temperature differential set

too low

Reset off differential according

to recommendation

Controller set to “on” position

Set system operation to

“Auto”

Pump operated but no fluid

flows from collectors

Air Scoop

System air-locked

Purge air from air scoop in

solar pump station by opening

valve slowly. Caution: after air

is evacuated fluid will flow out

in a small stream and may be

hot. Cover port with a rag to

catch any fluid.

Air vent

System air-locked

Open air vent on the top of the

system and purge excess air.

Close after purging.

Fluid

Loss of fluid from system

Locate leak and repair

Isolation valves

Valves in closed position

Open valves

Piping

Clogged or damaged piping

Unblock piping or repair

damaged piping

Pump

Broken impeller shaft

Replace shaft

Not vented properly

Install in correct orientation

Undersized

System piping run too long.

Refer to maximum piping

lengths and adjust

Noisy system

Air vents

Air trapped in system

Open air vent and purge air

scoop in solar pump station

by opening the valve slowly.

Caution: after air is evacuated

fluid will flow out in a small

stream and may be hot.

Cover port with a rag to catch

any fluid.

Pump

Bearings are dry or have

excessive wear

Lubricate or replace

Impeller loose

Tighten or replace impeller

Advertising