TROUBLESHOOTING

For your safety, water heater service should be performed only by a qualified service technician.

Read the GENERAL SAFETY INFORMATION section first

.

PROBLEM

POSSILBE MALFUNCTION

SERVICE TO BE PERFORMED

NOT ENOUGH OR NO HOT WATER

1) Blower will not run.

A) "ON/OFF" control switch turned off.

Turn switch to the on position.

B) Blower unplugged.

Plug blower back into 115 vac. outlet.

C) No power at outlet.

Repair service to outlet.

D) "ON/OFF" switch defective.

Replace switch.

E) Control harness defective.

Replace control harness.

F) Blower motor defective.

Replace blower and motor.

2) Blower running, burner not on

Replace switch.

A) Fan not running fast enough to close

air switch contacts.

Check for low voltage, less than 102 vac.,

have service checked and repaired.

B) Air pressure switch defective.

Replace switch.

C) Gas valve defective.

Replace gas control valve/ thermostat.

D) Control harness defective.

Replace harness.

E) Igniter defective.

Replace ignitor.

F) Unit has completed three trials to light

and fail.

Reset cycle by turning switch off and then

back on. If unit does not light in three tri-

als, contact a qualified person for service.

3) Thermostat problems

A) Thermostat set too low.

Set temperature control higher.

B) Thermostat or ECO defective.

Replace gas control valve/thermostat.

C) High limit control circuit open.

Replace high limit control.

4) Others

A) Heater undersized.

Reduce hot water usage.

B) Low gas pressure.

Contact a qualified person for service.

C) Incoming water is unusually cold.

Allow more time for heater to re-heat.

D) Leaking hot water pipes or fixtures.

Have plumber check and repair leaks.

CONDENSATION

A) Water on the floor under heater.

See "Condensation"

WATER LEAKS

Improperly sealed, hot or cold supply

connections, relief valve, drain valve or

thermostat threads.

Turn off heater & water, repair unit.

Leakage from other appliances or water

lines.

Inspect other appliances near water

heater.

Condensation of flue products.

Refer to "CONDENSATION"

LEAKING T&P VALVE

Thermal expansion in closed water sys-

tem

Install thermal expansion tank (DO NOT

PLUG T&P VALVE)

Improperly seated valves

Check relief valve for proper operation

(DO NOT PLUG T&P VALVE)

HOT WATER ODORS OR COLOR

(Refer to CATHODIC PROTECTION)

High sulfate or mineral content in water

supply or iron or sulfate reducing bacteria

in water supply

Drain and flush heater thoroughly, chlori-

nate, refil and flush again then chlorinate

water supply.