Where an existing chimney or vent is to be used, be sure

that the chimney or vent has adequate capacity for the

number and sizes of gas appliances being vented through

it. Inspect the chimney or vent and remove all soot or other

obstructions which will retard free draft.

Vent connectors making horizontal runs must have a minimum

upward slope toward the chimney or vent of 1/4 inch per foot.

Vent connector length should be kept as short as possible.

Be sure that the vent pipe does not extend beyond the inside

wall of a chimney.

In venting systems where a continuous or intermittent

back (positive) draft is found to exist, the cause must

be determined and corrected. In some cases, a special

vent cap may be required. Do not install this unit on the

positive draft side of a venting system being served by a

power exhauster.

water heater installation

Vent connection

Vent connections must be made to an adequate stack

or chimney. refer to the National Fuel Gas Code (current

edition) or to the vent pipe manufacturer’s gas vent and

chimney sizing table to properly design and size the venting

system. refer to Table 6 for the vent pipe size required for

installation to the barometric draft control assembly outlet.

table 6. barometric draft control

assembly outlet siZe

model

draft control

outlet diameter

GPG 81-140
GPG 81-199
GPG 81-270

GPG 81-370

6”
6”
8”
8”

water piping diagrams
This manual provides detailed water piping diagrams for typical

methods of application for the water heaters, see Water Piping

Diagrams beginning on page 35.
The water heater may be installed by itself, or with a separate

storage tank. When used with a separate storage tank, the

circulation may be either by gravity or by means of circulating

pump. Adjust flow by throttling a full port ball valve installed in the

circulating line on the outlet side of the pump. Never throttle flow

on the suction side of a pump. See the Water Piping Diagrams

beginning on page 35.
note: In addition to the factory installed Temperature-Pressure

relief Valve (T&P valve) on the water heater, each remote

storage tank that may be installed and piped to a water heating

appliance must also have its own properly sized, rated and

approved Temperature-Pressure relief Valve installed.
Call the toll free technical support phone number listed on the

back cover of this manual for further assistance in sizing a T&P

valve for remote storage tanks.

t&p ValVe discharge pipe

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

water line connections

The water piping installation must conform to these instructions

and to all local code authority having jurisdiction. Good practice

requires that all heavy piping be supported.
read and observe all requirements in the following sections

before installation of the water piping begins:
1. Water Temperature Control and mixing Valves on page 13.
2. Dishwashing machines on page 14.
3. Temperature-Pressure relief Valve on page 14-15.
4. Closed Systems and Thermal expansion on page 14.
5. For multiple water heater installations see Water Piping

Diagrams beginning on page 35.

water (potable) heating and space heating
1. All piping components connected to this unit for space

heating applications shall be suitable for use with potable

water.

2. Toxic chemicals, such as those used for boiler treatment,

shall NeVer be introduced into this system.

3. This unit may NeVer be connected to any existing heating

system or component(s) previously used with a non-potable

water heating appliance.

4. When the system requires water for space heating at

temperatures higher than required for domestic water

purposes, a tempering valve must be installed. Please

refer to installation diagrams beginning on page 35 of this

manual for suggested piping arrangements.

5. These water heaters cannot be used in space heating

applications only

thermometers (not supplied)
Thermometers should be obtained and field installed as shown

in the installation diagrams.
Thermometers are installed in the system as a means of

detecting the temperature of the outlet water supply.