Explosion hazard, Chemical hazard – State SBD85 365NE A User Manual

Page 33

Advertising
background image

33

Explosion Hazard

Flammable hydrogen gases

may be present.

Keep all ignition sources away

from faucet when turning on

hot water.

Do not smoke or have open flame or sparks in vicinity of heater.

Do not mix UN•LIME with other chemicals. Do not allow contact

with magnesium, aluminum or galvanized metals.

Chemical Hazard

• Product contains phosphoric acid.
• Keep out of reach of children.
• Use rubber or neoprene gloves.

Contains phosphoric acid. In case of external contact, flush with cool

water. If irritation persists, get medical attention. If swallowed, give 1

or 2 glasses of water or milk and call physician.
Get immediate medical attention for eyes. Keep out of reach of children.
note: the use of ruBBer or neoprene gloVes is

recommended, especially if you haVe any open

sores or cuts to aVoid unnecessary irritation or

discomfort.
1. Turn off fuel and/or power supply to heater. Also, turn off power

to any electrical device or equipment, which is attached, or part

of the system.

2. Open hot water side of faucet closest to heater and allow water

to run until it is cool enough to handle safely.

3. Close cold water inlet valve to heater.
4. Connect hose to drain valve at bottom of heater and start draining

heater into suitable floor drain area.

5. Remove pressure relief valve while heater is draining. NOTE:

Do not replace pressure relief valve until deliming is completed.

Pressure relief valve opening will also act as a vent in case of

possible contact between the delimer and the anode rod(s),

which may produce flammable hydrogen-air mixtures.

6. If pressure relief valve appears to be limed-up, place it in a clean

glass or plastic container adequate in size so that you can pour

enough UN•LIME® into container to cover the valve and allow

space for foaming. When foaming stops, run fresh cool water into

the container and rinse the pressure relief valve for a few minutes.

7. If heater does not drain completely after a reasonable length

of time, turn off the main water supply valve to stop water from

entering the tank due to a by-pass problem or defective cold

water inlet valve. Also, check for clogged drain valve opening.

Heater must be completely drained before introducing UN•LIME.

8. Remove the cleanout cover and place a clean plastic bucket

next to the cleanout opening.
Partially open the cold water inlet valve to allow time to

accomplish the following and then close the valve.

deliming solVents

UN•LIME is recommended for deliming. UN•LIME is a patented

food grade acid which is safe to handle and does not create the

harmful fumes which are associated with other products.
UN•LIME may be obtained from your dealer, distributor or

water heater manufacturer. Order Part Number 9005416105,

1 gallon, packed 4 gallons per case or Part Number 9005417105,

5 gallon container.
NOTE: Un•Lime is not available for use in Canada.
Hydrochloric base acids are not recommended for use on glass

lined tanks.
Observe handling instructions on label of product being used.

tank cleanout procedure

The following practices will ensure longer life and enable the

unit to operate at its designed efficiency:
1. Once a month the heater should be flushed. Open the drain

valve and allow two gallons of water to drain from the heater.

Inlet water valve should remain open to maintain pressure

in tank.

2. A cleanout opening is provided for periodic cleaning of the

tank. Gas must be shut off and heater drained before opening

cleanout.

To clean heater through cleanout opening, proceed as follows:
3. Drain heater.
4. Remove outer cover plate from lower side of heater jacket.
5. Remove six (6) hex head screws securing tank cleanout plate

and remove plate.

6. Remove lime, scale, or sediment using care not to damage

the glass lining.

7. Inspect cleanout plate gasket, if new gasket is required,

replace with part no. 9004099215.

8. Install cleanout plate. Be sure to draw plate up tight by

tightening screws securely.

9. Replace outer jacket cover plate.
In some water areas the sediment might not be removed by this

method and may result in the water heater making rumbling or

boiling noises. To dissolve and remove these more stubborn

mineral deposits, UN•LIME Professional Delimer should be used.

deliming using flo-jug method

UN•LIME in the 5 gallon size is recommended for deliming of all

models. Contact your local dealer, distributor or, water heater

manufacturer.

Prepare the Water Heater
To delime the water heater using the Flo-Jug method, first

prepare the heater for deliming.