Table 8. technical data venting, Continued) – State SBN85 390NE A User Manual

Page 19

Advertising
background image

19

model sBn100250ne/a

input: 250,000 Btu/hr

total Vent height (feet)

Vent Connector size: 6 inches

6 8 10 15 20 30 50 100

input Btuh/hr rise

Vent Connector diameter (inches)

250,000

1 Ft

8

8

7

7

7

6

6

6

250,000

2 Ft

7

7

7

7

6

6

6

6

250,000

3 Ft

7

7

7

7

6

6

6

6

number

Combined input

of heaters

in thousands of Btu/hr

manifold and Common Vent diameter (inches)

2

500,000

9

9

9

8

8

7

7

7

3

750,000

12

12

10

10

10

9

8

8

4

1,000,000

14

14

12

12

10

10

9

9

model sBn100275ne/a
input: 275,000 Btu/hr

total Vent height (feet)

Vent Connector size: 6 inches

6 8 10 15 20 30 50 100

input Btu/hr

rise

Vent Connector diameter (inches)

275,000

1 Ft

8

8

7

7

6

6

6

6

275,000

2 Ft.

8

8

7

7

6

6

6

6

275,000

3 Ft

7

7

7

7

6

6

6

6

number of

Combined input

heaters

in thousands of Btu/hr

manifold and Common Vent diameter (inches)

2

550,000

10

9

9

8

8

8

7

7

3

825,000

12

12

12

10

9

9

8

8

4

1,100,000

14

14

14

12

12

10

9

9

model sBn85310ne/a
input: 310,000 Btu/hr

t otal Vent height (feet)

Vent Connector size: 6 inches

6 8 10 15 20 30 50 100

input Btu/hr

rise

Vent Connector diameter (inches)

310,000

1 Ft.

9

8

8

8

7

7

6

6

310,000

2 Ft.

8

8

8

7

7

7

6

6

310,000

3 Ft.

8

8

8

7

7

7

6

6

number of

Combined input

heaters

in thousands of Btu/hr

manifold & Common Vent diameter

2

620,000

10

10

9

9

8

8

7

7

3

930,000

14

12

12

12

10

9

9

8

4

1,240,000

14

14

14

12

12

12

10

9

model sBn85366ne/a, sBn85390ne/a

input: 366,000, 390,000 Btu/hr

total Vent height (feet)

Vent Connector size: 6 inches

6 8 10 15 20 30 50 100

input Btu/hr

rise

Vent Connector diameter (inches)

366,000

1 Ft

9

9

9

8

8

8

8

8

390,000

1 Ft

10

9

9

9

8

8

8

8

366,000

2 Ft

9

9

8

8

8

8

8

8

390,000

2 Ft

9

9

9

8

8

8

8

8

366,000

3 Ft

9

8

8

8

8

8

8

8

390,000

3 Ft

9

9

8

8

8

8

8

8

number of

Combined input

heaters

in thousands of Btu/hr

manifold & Common Vent diameter (inches)

2

732,000

12

10

10

9

9

9

8

8

780,000

12

12

10

10

9

9

8

8

3

1,098,000

14

14

14

12

12

10

9

9

1,170,000

14

14

14

12

12

10

10

9

4

1,464,000

16

16

14

14

14

12

12

10

1,560,000

16

16

16

14

14

12

12

10

taBle 8. teChniCal data Venting

(Continued)

Advertising