Troubleshooting – Haws 8111FP User Manual

Page 2

Advertising
background image

12/09

Model 8111FP

Page 2 of 4


LOCATION OF UNIT: The Model 8111FP Drench Shower should be installed in
close proximity to potential accident areas. It should be clearly identified, free from
obstructions and easy to access.

SUPPLY LINE: The minimum recommended line size is 1” IPS with 30-90 psi (2-6
ATM) flowing pressure. Where sediment or mineral content is a problem, an inlet
filter is recommended.

PLUMBING CONNECTIONS: Inlet supply is female 1” IPS.

TROUBLESHOOTING

PROBLEM

REPAIR CHECKLIST

1. No flow.

1.

Check the main shut-off valve.

2. Insufficient water flow.

2. a. Verify minimum 30 psi (2 ATM)

flowing supply line pressure.

b. Probable clogging of flow control

inside showerhead. Unscrew
showerhead off of elbow and clean
rubber flow control.










For more information about Haws products, see our website:

www.hawsco.com
















© 2009 Haws® Corporation – All Rights Reserved
HAWS® and other trademarks used in these materials are the exclusive property of Haws Corporation.

Advertising