Chapter 3 ____________________________________________ Humidity Measurement in Concrete
VAISALA _______________________________________________________________________ 23
1111-091
Figure 7
Plugged Tube in Fresh Concrete
4.
When the concrete has hardened, remove the plug and the flange
from the tube. Leave the tube in place.
5.
Use a flat-head screwdriver or other suitable tool to crack the
concrete at the bottom of the tube. This is necessary because during
the curing of the concrete a solid surface forms in the bottom of the
tube. Cracking this surface helps the air in the tube to reach
equilibrium with the humidity in the concrete. See Figure 8 below.
1111-092
Figure 8
Cracking the Concrete at the Bottom of the Tube