Configuration commands related to modbus, Table 9, Configuration commands for modbus rtu – Vaisala DPT145 User Manual

Page 46

Advertising
background image

User's Guide _______________________________________________________________________

46 ___________________________________________________________________ M211371EN-D

Configuration Commands Related to Modbus

In addition to enabling the Modbus protocol in the device, Modbus over

RS-485 needs the following software settings: serial bit rate, parity,

number of stop bits, and Modbus device address.

Use the service commands listed in Table 9 below to configure the

Modbus RTU using the USB service cable.

Table 9

Configuration commands for Modbus RTU

Service Command Description

SMODE MODBUS Enable Modbus communication protocol.

See section Set Serial Line Operating Mode on page

41.

SERI b p 8 s

Change baud rate and parity.

b = baud rate (minimum 9600 when using Modbus)

p = parity (E, N, or O)

8 = number of data bits must be 8

s = number of stop bits (2 if parity is N, 1 otherwise*)

See section Set Serial Line Settings on page 42.

ADDR a

Set Modbus address.

a = new address (0…255)**

See section Set Transmitter Address on page 42.

SDELAY d

Add extra Modbus response delay.***

d = new delay in units of 1/250 seconds (0…255)

See section Set Serial Line Response Time on page 43.

* Modbus specification defines that two stop bits must be used if parity is N.

** Setting address to zero switches the instrument offline from the Modbus bus.

Addresses 248 … 255 are not supported by the Modbus standard but DPT145 works

with them.

*** Extra response delay can be used, for example, to avoid problems caused by

direction-switching delays in bus converters.

NOTE

The instrument must be switched off and on before the configuration

changes made with the service cable take effect.

Advertising