MOUNTING INSTRUCTIONS

This operator interface is primarily designed for

through-panel mounting. Four VESA mount tapped screw-

holes (M4 x 0.7, 5 mm deep) are present on the rear of the

panels to allow for stand or wall mounting. Care should be

taken to remove any loose material from the mounting cut-

out to prevent that material from falling into the operator

interface during installation. A gasket is provided to enable

sealing to NEMA 4X/IP66 specification. Install the nine

mounting clips provided and tighten to 6.0 pound-force inch

(96 ounce-force inch) evenly for uniform gasket compression.

CONNECTING TO EARTH GROUND

Each operator panel has a chassis ground terminal on the back of the unit.

Your unit should be connected to earth ground (protective earth).

The chassis ground is not connected to signal common of the unit.

Maintaining isolation between earth ground and signal common is not required

to operate your unit. But, other equipment connected to this unit may require

isolation between signal common and earth ground. To maintain isolation

between signal common and earth ground care must be taken when connections

are made to the unit. For example, a power supply with isolation between its

signal common and earth ground must be used. Also, plugging in a USB cable

may connect signal common and earth ground.

1

1

USB’s shield may be connected to earth ground at the host. USB’s shield in

turn may also be connected to signal common.

POWER SUPPLY REQUIREMENTS

The G12 requires a 24 VDC power supply. Your unit may draw considerably

less than the maximum rated power depending upon the features being used. As

additional features are used your unit will draw increasing amounts of power.

Items that could cause increases in current are modules, additional on-board

communications, SD card, and other features programmed through Crimson.

In any case, it is very important that the power supply is mounted correctly if

the unit is to operate reliably. Please take care to observe the following points:

– The power supply must be mounted close to the unit, with usually not more

than 6 feet (1.8 m) of cable between the supply and the operator interface.

Ideally, the shortest length possible should be used.

– The wire used to connect the operator interface’s power supply should be

at least 22-gage wire suitably rated for the temperatures of the environment

to which it is being installed. If a longer cable run is used, a heavier gage

wire should be used. The routing of the cable should be kept away from

large contactors, inverters, and other devices which may generate

significant electrical noise.

– A power supply with an NEC Class 2 or Limited Power Source (LPS) and

SELV rating is to be used. This type of power supply provides isolation to

accessible circuits from hazardous voltage levels generated by a mains

power supply due to single faults. SELV is an acronym for “safety extra-

low voltage.” Safety extra-low voltage circuits shall exhibit voltages safe

to touch both under normal operating conditions and after a single fault,

such as a breakdown of a layer of basic insulation or after the failure of a

single component has occurred.

FOOT MAY BE REMOVED

FOR THICKER PANEL

INSTALLATIONS

ALL NONINCENDIVE CIRCUITS MUST BE

WIRED USING DIVISION 2 WIRING

METHODS AS SPECIFIED IN ARTICLE 501-4

(b), 502-4 (b), AND 503-3 (b) OF THE

NATIONAL ELECTRICAL CODE, NFPA 70

FOR INSTALLATION WITHIN THE UNITED

STATES, OR AS SPECIFIED IN SECTION

19-152 OF CANADIAN ELECTRICAL CODE

FOR INSTALLATION IN CANADA.

11.458 (291.0)

7.561

(192.0)

4X R.10 (2.5)

MAX.

All tolerances ±.059" (±1.5 mm)

The protective conductor terminal is bonded to conductive

parts of the equipment for safety purposes and must be

connected to an external protective earthing system.

O

peratOr

I

nterface

I

nstallatIOn

PANEL CUT-OUT

I/O MODULE INSTALLATION

Modules must be installed beginning with slot 1 (left-most slot), with no

empty slots between the modules, and the order must match the modules order

in the Crimson database. Torque screws to 6.0 pound-force inch (96 ounce-

force inch).

REMOVE RUBBER

MODULE PLUG

WARNING: Disconnect all power

to the unit before installing or

removing modules.

2.95 (75)

1.48 (37.5)

1.08

(27.4)

2.95

(75)

VESA MOUNT (MIS-D 75) DIMENSIONS