Red Lion GMUIN4 Universal Input Module User Manual

General description, Configuration, Safety summary

Advertising
background image

1

DEDICATED 4 UNIVERSAL INPUT MODULE FOR THE

GRAPHITE SERIES

ACCEPTS THERMOCOUPLES, RTDs, 0/4-20 mA AND 0-10 V

SIGNAL INPUTS

OFFERS COMPLETE ISOLATION; INPUTS, POWER AND CORE

IDEAL FOR DATA-ACQUISITION APPLICATIONS

CAN BE USED IN CONJUNCTION WITH ANY GRAPHITE

MODULES

GENERAL DESCRIPTION

The model GMUIN4 is a 16-bit analog input module designed for use with the

Graphite Series. The module provides 4 isolated universal analog inputs as a

means of signal measurement for data-acquisition. The GMUIN4 accepts a wide

range of thermocouples and RTDs, as well as 0/4-20 mA and 0-10 V process

signals. The modules connect and communicate via proprietary USB connection

to the various Graphite devices. The Graphite devices, equipped with serial ports

as well as an Ethernet port(s), allows the system to share data with PCs, PLCs, and

SCADA systems. The maximum number of modules varies for each Graphite

device, see specific models for details.

Once programmed, the module will continue to operate independent of the

Graphite device as long as power is applied. Remove power from the host device

before installing or replacing any modules.

CONFIGURATION

The Graphite Series is configured with Windows

®

compatible Crimson

®

software. The software is an easy to use, graphical interface which provides a

means of configuration and commissioning of new systems, as well as routine

module re-calibration.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to

prevent damage to either the instrument or equipment connected to it. If

equipment is used in a manner not specified by the manufacturer, the protection

provided by the equipment may be impaired.

Do not use the module to directly command motors, valves, or other actuators

not equipped with safeguards. To do so can be potentially harmful to persons or

equipment in the event of a fault to the module. An independent and redundant

temperature limit indicator with alarm outputs is strongly recommended.

SPECIFICATIONS

1. POWER: Power will be supplied by the Graphite host device.

2. LEDs:

STS - Status LED shows module condition.

AL1, AL2, AL3, AL4 - Alarm LEDS are lit during any input alarm

condition.

3. MEMORY: Non-volatile memory retains all programmable parameters.

4. ISOLATION LEVEL: 500 Vrms @ 50/60 Hz for 1 minute between each

Signal Input and the host Power Supply Input.

5. COMMUNICATIONS: Provided by the Graphite host device

6. INPUTS

Effective Resolution: Full 16-bit

Sample Time: 50 msec

Common Mode Rejection: >110 dB, 50/60 Hz

Normal Mode Rejection: >50 dB, 50/60 Hz

Temperature Coefficient: 0.01%/°C

Step Response Time: 100 msec typ., 200 msec max.

7. THERMOCOUPLE INPUTS:

Types: T, E, J, K, R, S, B, N, C

Slope & Offset: Provides sensor error correction

Input Impedance: 20 M Ω

Lead Resistance Effect: 0.25 µV/Ω

MODEL GMUIN4 - GRAPHITE™ SERIES UNIVERSAL

INPUT MODULE

Bulletin No. GMUIN4-C
Drawing No. LP0923
Released 04/14

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

CAUTION: Risk of Danger.

Read complete instructions prior to

installation and operation of the unit.

CAUTION: Risk of electric shock.

4.65

(118)

2.97 (76)

1.25 (32)

DIMENSIONS In inches (mm)

C

US LISTED

UL

R

IND. CONT. EQ.

34AD

Advertising