Red Lion Data Station Plus User Manual

Model dsp – data station plus, General description, Safety summary

Advertising
background image

1

PROTOCOL CONVERSION FEATURE CONVERTS NUMEROUS

PROTOCOLS SIMULTANEOUSLY

COMPACTFLASH

®

SLOT ALLOWS PROCESS DATA TO BE

LOGGED DIRECTLY TO CSV FILES

VIRTUAL HMI OFFERS BUILT-IN PC-BASED SCADA

FUNCTIONALITY

WEBSERVER PROVIDES WORLDWIDE ACCESS TO DATA

LOGS AND VIRTUAL HMI

EXTENSIVE BUILT-IN DRIVER LIST ALLOWS EASY DATA

MAPPING TO PLCs, PCs, AND SCADA SYSTEMS

ALARM NOTIFICATIONS CAN BE SENT VIA EMAIL OR TEXT

MESSAGES

10 BASE-T/100 BASE-TX ETHERNET CONNECTION

CAN CONNECT TO AN UNLIMITED NUMBER OF

DEVICES VIA FOUR PROTOCOLS SIMULTANEOUSLY

GENERAL DESCRIPTION

The Data Station Plus was designed to act as a nexus for industrial data

collection and management. The unit offers multiple protocol conversion, data

logging and remote machine access. With three built in serial ports and a 10

Base-T/100 Base-TX Ethernet port, the unit performs protocol conversion,

allowing disparate devices to communicate seamlessly with one another. The

Ethernet port supports up to four protocols simultaneously so even Ethernet to

Ethernet protocols can be converted.

The CompactFlash card allows data to be collected and stored for later

review. The files are stored in simple CSV file format allowing common

applications, such as Microsoft Excel and Access, to view and manage the data.

The free Websync utility provides a means to synchronize the files with a PC’s

hard drive for permanent storage. The CompactFlash card may also be used to

load new configuration files into the Data Station.

The built-in web server allows log files to be retrieved manually, and also

provides access to the unique “virtual HMI”. The virtual HMI is programmed

just like Red Lion’s G3 series of HMI. Any standard web browser such as

Internet Explorer or Netscape may be used to monitor or control the HMI from

a PC anywhere in the world.

The USB port may be used for blazing fast file downloads, or to mount the

Data Station’s CompactFlash card as an external drive to your PC.

The Data Station’s DIN rail mounting saves time and panel space and snaps

easily onto standard top hat (T) profile DIN rail.

SOFTWARE

The Data Station is programmed with Crimson

®

2.0 software for Windows

®

2000 or later platforms. The software is an easy to use graphical interface which

can be purchased as part of a kit that includes a manual and cables, or

downloaded free of charge from www.redlion.net.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to

prevent damage to either the instrument or equipment connected to it. If

equipment is used in a manner not specified by the manufacturer, the protection

provided by the equipment may be impaired.

Do not use the controller to directly command motors, valves, or other

actuators not equipped with safeguards. To do so can be potentially harmful to

persons or equipment in the event of a fault to the controller. An independent

and redundant temperature limit indicator with alarm outputs is strongly

recommended.

CompactFlash is a registered trademark of CompactFlash Association.

MODEL DSP – DATA STATION PLUS

Bulletin No. DSP-K
Drawing No. LP0629
Released 11/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

CAUTION: Risk of Danger.

Read complete instructions prior to

installation and operation of the unit.

5.30 (134.7)

RS232

ETHERNET

CF

STS

USB/PG

RS485

RS232/PG

3.09 (78.5)

4.15 (105.4)

DIMENSIONS In inches (mm)

FOR USE IN HAZARDOUS LOCATIONS:

Class I, Division 2, Groups A, B, C, and D

C

US LISTED

UL

R

3PWL

PROGRAMMABLE

CONTROLLERS

C

US LISTED

UL

R

IND. CONT. EQ.

34AD

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF

COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,

DIVISION 2

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I,

DIVISION 2, GROUPS A, B, C, D, OR NON-HAZARDOUS

LOCATIONS ONLY