9. CONTROL INPUTS:

Programmable user inputs (3): Internal 10 K

W pull-up to +5 VDC,

V

IL

= 1.0 V

MAX

; V

IH

= 4.0 V

MIN

, response time = 10 msec max.

Inhibit: Internal 10 K

W pull-up to +5 VDC, V

IL

= 1.0 V

MAX

;

V

IH

= 4.0 V

MIN

.

10. SERIAL COMMUNICATIONS:

Type: RS485 Multi-point Balanced Interface.

(Can connect up to 32 units on a line.)

Baud Rate: Programmable from 1200 to 9600.
Maximum Addresses: Programmable from 00 to 99.

(Actual number on a line is limited by hardware specifications.)

Transmit Delay: Programmable for 0.002 or 0.100 second.
Data Format:

10 Bit Frame; 1 start bit, 7 data bits, 1 parity bit, and 1 stop bit.
Parity is programmable for either ODD, EVEN, or No Parity.

11. OUTPUT(S):

Solid-State: Current sinking NPN open collector transistor.
V

CE

= 1 V

SAT

@ 100 mA maximum. V

OH

= 30 VDC maximum.

(Internal Zener Diode Protection).
Relay(s): Mounted on field-replaceable P.C. board. Form C contacts rated
at 5 amps @ 120 VAC/240 VAC or 28 VDC (resistive load), 1/8 H.P. @
120 VAC (inductive load). The operate time is 5 msec nominal and the
release time is 3 msec nominal.
Life Expectancy: 100,000 cycles at maximum load rating. (Decreasing
load and/or increasing cycle time, increases life expectancy.)
Programmable Timed Output(s): Programmable time ranges from 0.01
to 99.99 seconds, ±0.05% - 11 msec. max.
Count Boundary Output Response Time: 10 msec

12. CERTIFICATIONS AND COMPLIANCES:

SAFETY

IEC 6 1 0 1 0 -1 , EN 6 1 0 1 0 -1 : S a f e t y req u i remen t s f o r e l e c t ric a l

equipment for measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529
Type 4X Indoor Enclosure rating (Face only), UL50

ELECTROMAGNETIC COMPATIBILITY

Immunity to EN 50082-2
Electrostatic discharge

EN 61000-4-2

Level 2; 4 Kv contact
Level 3; 8 Kv air

Electromagnetic RF fields

EN 61000-4-3

Level 3; 10 V/m
80 MHz - 1 GHz

Fast transients (burst)

EN 61000-4-4

Level 4; 2 Kv I/O

1

Level 3; 2 Kv power

RF conducted interference

EN 61000-4-6

Level 3; 10 V/rms

1

150 KHz - 80 MHz

Power frequency magnetic fields

EN 61000-4-8

Level 4; 30 A/m

Emissions to EN 50081-2
RF interference

EN 55011

Enclosure class A
Power mains class A

Note:
1. When the unit is DC powered from terminal TBA pin 5 (common) and

terminal TBA pin 3 (DC OUT/IN) a power line filter was installed, RLC
#LFIL0000 or equivalent, so as not to impair the function of the unit.

13. ENVIRONMENTAL CONDITIONS:

Operating Temperature: 0 to 50°C
Storage Temperature: -40 to 70°C
Operating and Storage Humidity: 85% max. (non-condensing) from
0°C to 50°C.
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
direction for 1.5 hours, 2 g.
Shock According to IEC 68-2-27: Operational 20 g (10 g relay), 11 msec
in 3 directions.
Altitude: Up to 2000 meters.

14. CONSTRUCTION: High impact plastic case with clear viewing

window. The front panel meets NEMA 4X/IP65 requirements for indoor
use when properly installed. Installation Category II, Pollution Degree 2.
Panel gasket and mounting clips included.

15. WEIGHT: 1.5 lbs. (0.68 Kg)