In many industrial applications, a meter is required to totalize the output of an

operation or event. The pulses from a sensor are received by the PAXLC, and
then totalized on the display. In many cases the incoming pulses do not represent
the desired display readout. For those applications, a scale factor can be entered
into the meter, scaling the pulses to obtain the desired readout. The following
formula will help provide the scaling values to achieve the desired readout.

SF = DR
EPU

WHERE:

SF = Scale Factor
DR = Desired Readout* (Single unit of measure, i.e. foot, gallon, etc.)
EPU = Existing Pulses per Unit (Number of pulses per single unit of
measure,

i.e. foot, gallons, etc.)

*For applications requiring a decimal point, select and program the

appropriate decimal point. When calculating the Scale Factor, use the whole
value of the number to be displayed, for example, 1.0 feet, the Desired
Readout in this case is 10. Do not use decimal points in the Scaling Formula.

For calculated SF values less than 9.99999

If the Scale Factor is a value less than 9.99999, it can be entered directly

into the meter as the Scale Factor and the Scale Multiplier can be left at 1.

For calculated SF values greater than 9.99999

If the Scale Factor is a value over 9.99999 (maximum value), the Scale

Multiplier must be used to reduce the calculated SF value until it is less then
9.99999. The Scale Multiplier multiplies the calculated Scale Factor value by
1, 0.1, and 0.01, thus reducing the calculated value accordingly. Select the
appropriate Scale Multiplier value that allows the Scale Factor to be a value
under 9.99999. Both the Scale Factor and Scale Multiplier can then be
entered into the meter.

Example 1:

This application involves counting cases from a production line. The sensor

provides a pulse for every can produced. The desired readout is in cases,
therefore the incoming pulses need to be converted to obtain the proper readout.
The following is used to calculate scale factor.

SF = DR
EPU

DR = 1 case
EPU = 12 cans/case

SF = 1
12

SF = 0.083333

Since the Calculated Scale Factor Value is less than 9.99999, it can be

entered directly into the meter. The Scale Multiplier can be left at 1.

Front Panel Reset

No Function

Access Programming Mode

PAR

PROGRAMMING MODE OPERATION

DISPLAY MODE OPERATION

KEY

Store selected parameter and index to next parameter

Increment selected digit of parameter value

Select digit position in parameter value

Advertising
This manual is related to the following products: