Red Lion PAXLT User Manual

Model paxlt - pax lite temperature meter, General description, Safety summary

Advertising
background image

5 DIGIT, 0.56" HIGH RED LED DISPLAY

DISPLAYS °C OR °F WITH 1° OR 0.1° RESOLUTION

BACKLIGHT OVERLAYS INCLUDED (°C AND °F)

MAX AND MIN READING MEMORY

TC COLD JUNCTION COMPENSATION (ON/OFF)

PROGRAMMABLE TEMPERATURE OFFSET

PROGRAMMABLE USER INPUT

DUAL 5 AMP FORM C RELAYS

UNIVERSALLY POWERED

NEMA 4X/IP65 SEALED FRONT BEZEL

THERMOCOUPLE AND RTD INPUTS

CONFORMS TO ITS-90 STANDARDS

GENERAL DESCRIPTION

The PAXLT is a versatile meter that accepts a variety of thermocouple and

RTD inputs and provides a temperature display in Celsius or Fahrenheit. The

readout conforms to ITS-90 standards, with 1° or 0.1° resolution. The 5-digit

display has 0.56" high digits with adjustable intensity. Backlight overlay labels

for °F and °C are included.

The meter features a Maximum and Minimum reading memory, with

programmable capture time. The capture time is used to prevent detection of

false max or min readings which may occur during start-up or unusual process

events. Either value can be displayed if desired. The display can be toggled

manually or automatically between the selected values.

Other features include thermocouple cold junction compensation, display

offset and a programmable user input to perform a variety of meter control

functions. Two setpoint outputs are provided, each with a Form C relay. Output

modes and setup options are fully programmable to suit a variety of control

requirements.

The PAXLT can be universally powered from a wide range of AC or DC

voltage. The meter has been specifically designed for harsh industrial

environments. With a NEMA 4X/IP65 sealed bezel and extensive testing to meet

CE requirements, the meter provides a tough yet reliable application solution.

SAFETY SUMMARY

All safety regulations, local codes and instructions that appear in this and

corresponding literature, or on equipment, must be observed to ensure personal

safety and to prevent damage to either the instrument or equipment connected to

it. If equipment is used in a manner not specified by the manufacturer, the

protection provided by the equipment may be impaired.

Do not use this meter to directly command motors, valves, or other actuators

not equipped with safeguards. To do so can be potentially harmful to persons or

equipment in the event of a fault to the meter

SPECIFICATIONS

1. DISPLAY: 5 digit, 0.56" (14.2 mm) intensity adjustable Red LED
2. POWER REQUIREMENTS:

AC POWER: 50 to 250 VAC 50/60 Hz, 12 VA

Isolation: 2300 Vrms for 1 min. to all inputs and outputs

DC POWER: 21.6 to 250 VDC, 6 W

3. READOUT:

Display Range: -19999 to 99999

Scale: °F or °C

Resolution: 1° or 0.1°

Response Time: 500 msec min.

Display Overrange/Underrange Indication: "….." / "-…."

Input Overrange/Underrange Indication:  / 

1

3.60 (91.4)

(96.5)

3.80

1.95

(49.5)

(2.5)

.10

(104.1)

4.10

(44.5)

1.75

PAR

9

1

3

2

4 5 6 7 8

10

13

11 12

14 15

SEL RST

SP1

SP2

8.8.8.8.8

X

MA

I

M N

MODEL PAXLT - PAX LITE TEMPERATURE METER

DIMENSIONS In inches (mm)

Bulletin No. PAXLT-A
Drawing No. LP0750
Released 04/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

CAUTION: Risk of Danger.

Read complete instructions prior to

installation and operation of the unit.

CAUTION: Risk of electric shock.

ORDERING INFORMATION

MODEL NO. DESCRIPTION

PART NUMBER

PAXLT0U0

PAXLT000

PAXLT

Note: Recommended minimum clearance (behind the panel) for mounting clip installation is

2.1" (53.4) H x 5.0" (127) W.

TC/RTD Temperature Meter with Dual Relay Output

C

US LISTED

UL

R

51EB

IND. CONT. EQ.

For Model No. PAXLT0U0 Only

UL Listed TC/RTD Temperature Meter with Dual

Relay Output

Advertising