Pro.dis – Red Lion C48T User Manual

Page 17

Advertising
background image

There are several ways to limit the programming of parameters from the front

panel keypad. The Accessible Value parameter is used with the Program Disable
plug jumper and an external programmable User Input selected for

Pro.dis

to

limit programming. To enter the programming mode, a code number may need

to be entered, depending on the Program Disable Setting. Front Panel Function
Key F1 cannot be selected for program disable. The following table describes
the possible program disabling functions.

-11-

Front Panel Accessible Functions With Program Disable

PGM.DIS.

JUMPER

USER INPUT TERMINAL

PROGRAM CODE

NUMBER

PROTECTED VALUE

MENU

OPERATOR ACCESS AT

MAIN DISPLAY

PROGRAM

DISABLE LEVEL

PROGRAMMING

ENABLED

OFF (EN)

INACTIVE or Not
Programmed for Pro.dis

ALL

No

All displayed values
changeable

None

Yes

OFF (EN) ACTIVE

0

No

Per Access Privileges
programmed

Level 1

No

OFF (EN) ACTIVE

1 to 99

Yes

W/code

Per Access Privileges
programmed

Level 1

No

OFF (EN) ACTIVE

100 to 199

No

Per Access Privileges
programmed

Level 1

Yes

W/code

ON (DIS)

INACTIVE or Not
Programmed for Pro.dis

0

No

Per Access Privileges
programmed

Level 1

No

ON (DIS)

INACTIVE or Not
Programmed for Pro.dis

1 to 99

Yes

W/code

Per Access Privileges
programmed

Level 1

No

ON (DIS)

INACTIVE or Not
Programmed for Pro.dis

100 to 199

No

Per Access Privileges
programmed

Level 1

Yes

W/code

ON (DIS) ACTIVE

ALL

No

Viewable only

Level 2

No

C48t-im.QXD 3/5/04 3:28 PM Page 11