Red Lion PSA - INDUCTIVE User Manual

Inductive proximity sensors, Description & operation, Models psa-1b & 2b

Advertising
background image

1

.256

(6.5)

DIA.

1.181 (30)

6.56

(2 METERS)

CHROMED

BRASS CASE

PVC JACKET

2-CONDUCTORS

#24 AWG

.118 (3.0)

1.18

1.57 (40)

1.74 (44)

PVC JACKET

LED

#20 AWG

2 CONDUCTORS

6.56' (2 METERS)

1.42 (32) ACROSS FLATS

.39 (10) THICKNESS

PLASTIC CASE & JAM NUTS

(30)

M30 X 1.5

(ISO 68 METRIC

STRAIGHT THREADING)

SENSE FERROUS & NON-FERROUS METAL OBJECTS TO

“ZERO SPEED”

2-WIRE CURRENT SOURCE (NAMUR) & 3-WIRE NPN TRUE

OPEN COLLECTOR OUTPUTS

5 SIZES & 3 SENSING DISTANCES FOR APPLICATION

VERSATILITY

L.E.D. TARGET INDICATOR (PSA 2B, 6B, 7B, & 8B)

INDUCTIVE PROXIMITY SENSORS

METAL TARGET

CIRCUIT

OSC.

COIL

PSA 1B, 2B

BRN

BLUE

> 2.2mA-NO METAL
< 1mA-METAL SENSED

+VDC

CNT.

Vs

Rs

Figure 2

Bulletin No. PSAB-D
Drawing No. LP0443
Released 05/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

DESCRIPTION & OPERATION

Inductive Proximity Sensors detect the presence of metal objects which come

within range of their oscillating field and provide target detection to “zero

speed”. Internally, an oscillator creates a high frequency electromagnetic field

(RF) which is radiated from the coil and out from the sensor face (See Figure

1). When a metal object enters this field, eddy currents are induced into

the object.

As the metal moves closer to

the sensor, these eddy currents

increase and result in an absorption

of energy from the coil which

dampens the oscillator amplitude

until it finally stops.

MODELS PSA-1B & 2B

The 2-wire Models PSA-1B and 2B contain only the coil and oscillator

circuit (See Figure 2). With no metal object being sensed, the circuit oscillates

and draws greater than 2.2 mA of supply current. As a metal object of sufficient

size is brought into the sensing field, the oscillator amplitude dampens and

finally stops, resulting in less than 1 mA of circuit current being drawn. This

greater than 2.2 mA to less than 1 mA change in circuit current between

oscillating and non-oscillating conditions is converted into a usable voltage

signal (V

S

) by placing a resistor (R

S

) in series with the sensor leads.

MET

AL

TA

RGET

CIRCUIT

OSC.

SENSING FIELD

] PSA1B, or 2B OUTPUT

] PSA6B, 7B, or 8B OUTPUT

OUTPUT ON

<1mA

OSCILLATOR STALLED

AMPLITUDE

ABSENT

TARGET

>2.2mA

OUTPUT OFF

SENSOR

TARGET APPROACHING

TARGET PRESENT

TARGET ABSENT

Figure 1

PSA-1B & PSA-2B SPECIFICATIONS

1. Power Supply:

PSA-1B

PSA-2B

+5 to +30 VDC

2. Maximum Switching Frequency:

5 KHz

500 Hz

3. Output:

Less than 1 mA Target Sensed; Greater

than 2.2 mA No Target.

4. Maximum Sensing Distance:

0.059" (1.5 mm)

0.394" (10 mm)

5. Wire Color Code:

Brown = +VDC; Blue = Count

6. Operating Temperature:

-25°C to +70°C (-13°F to +158°F)

7. Construction:

NEMA 1, 3, 4, 6, 13, and IEC IP 67.

DIMENSIONS In inches (mm)
PSA-1B

PSA-2B

Advertising