Red Lion LFIL User Manual

Model lfil - general purpose line filter, Description, Specifications

Advertising
background image

ORDERING INFORMATION

DESCRIPTION

This line filter can be used in AC or DC power supply lines to attenuate

conducted Electro-Magnetic Interference (EMI). EMI is the most common
cause of erratic operation in electronic equipment. Line filters should be
installed close to electronic equipment and mounted directly to a metal
enclosure that is connected to earth ground (protective earth).
Note: Always connect the earth lead of the filter to the power line ground

(protective earth).

The ideal location for the line filter is directly inside the metal enclosure in

which the unit is mounted when the source of EMI is external to the enclosure
(See Figure 1). Mount the filter where the power enters the enclosure. If the
enclosure contains many different types of equipment or EMI generating
devices, such as motors or contactors, then the EMI source may be inside the
enclosure. In this case, mount the line filter as close to the unit as possible (See
Figure 2).

SPECIFICATIONS

1. CURRENT RATING: 1.15 A @ 25

C ; 1 A @ 40

C

2. LEAKAGE CURRENT: 0.74 mA/Lead @ 230 V, 50 Hz
3. INDUCTANCE: 12 mH
4. CONNECTIONS: Flexible wires 20 AWG
5. HIPOT TEST VOLTAGE: P→E: 2 KV for 2 sec

P→N: 760 VAC for 2 sec

6. MAX OPERATING VOLTAGE: 250 VAC, 50/60 Hz
7. OPERATING FREQUENCY: DC to 400 Hz
8. TEMPERATURE RANGE: -25

C to +100

C

9. WEIGHT: 2.29 oz. (65 g)

UL recognized component

(Schaffner, PN# FN2010-1/07, File # E64388)

MODEL LFIL - GENERAL PURPOSE LINE FILTER

1.73 (44)
2.13 (54)
2.52 (64)

0.248 (6.3)

1.4 (35)

(5.3)

0.96 (24.3)

0.21

DIMENSIONS In inches (mm)

.033µF

2200pF

2200pF

POWER LINE

EQUIPMENT

P(+)

N(-)

PE

P(+)

N(-)

(BROWN)

(BLUE)

(YEL/GRN)

(BROWN)

(BLUE)

MODEL NO.

DESCRIPTION

PART NUMBER

LFIL

General Purpose Line Filter

LFIL0000

BLOCK DIAGRAM

EARTH

METAL ENCLOSURE

SIDE VIEW

GROUND

1

2

3

4

5

6

7

8

9

10

13

14

12

11

EARTH

GROUND

METAL PANEL

REAR VIEW

BROWN

BLUE

YEL/GRN

AC

POWER

FEED

BLUE

BROWN

Figure 1

Figure 2

If the panel and enclosure are non-conductive, then the power feed ground is

the only earth ground connection. Connecting only the earth lead of the filter to
the earth ground without mounting the filter directly to a metal enclosure will
not be as effective.

Bulletin No. LFIL-A
Drawing No. LP0380
Released 02/12

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

Do not dispose of unit in trash - Recycle

Advertising