Red Lion ILS User Manual

Inductive load suppressor, Description, Ordering information

Advertising
background image

1

DESCRIPTION

These devices, when installed across an inductive load, such as a contactor,

solenoid or relay, will suppress transient surges during a switching. This will

enhance relay life and provide increased reliability of operation.

There are two devices available, one for use in 115 volt circuits and one for

use in 230 volt circuits.

INDUCTIVE LOAD SUPPRESSOR

Fully slide PVC insulating tubing over Model ILS leads, as shown.

Caution: Ensure VAC is “OFF” before installing Model ILS.

ILS

ORDERING INFORMATION

ILS SPECIFICATIONS *

*

NOTE: These devices will suppress most transient surges. However, if the device heats up or stops functioning after a short period of time a higher joules rated device may be required.

Bulletin No. ILS1/2-D
Drawing No. LP0151
Released 06/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

MODEL NO.

DESCRIPTION

PART NUMBER

ILS1

115 VAC Inductive Load Suppressor

ILS11500

ILS2

230 VAC Inductive Load Suppressor

ILS23000

RATED VOLTAGE

DEVICE MODEL

NUMBER

AC VOLTS

DC VOLTS

SINGLE PULSE

TRANSIENT

ENERGY JOULES

POWER DISSIPATION

WATTS

CLAMPING VOLTAGE

VOLTS

RATED PEAK

SINGLE PULSE

TRANSIENT CURRENT (AMPS)

ILS1

130

175

6500

80

1.0

340 V @ 100 A

ILS2

275

370

6500

150

1.0

710 V @ 100 A

Do not dispose of unit in trash - Recycle