Red Lion APSIS User Manual

Model apsis, Provides, Description

Advertising
background image

PROVIDES...

!

24 VDC UNREGULATED “HELPER” SUPPLY FOR LOAD
SHARING WITH OTHER 24 VOLT SYSTEMS WITH UNUSUAL
SENSOR AND ACCESSORY LOADS OR...

!

“STAND-ALONE” APPLICATIONS FOR POWERING +24 VDC
SENSORS AND ACCESSORIES OR...

!

TWO 20 mA CURRENT SOURCES, EACH CAPABLE OF
SUPPLYING 20 mA OF CURRENT FOR SERIAL
COMMUNICATION LOOPS AND POWERING UP TO 16 UNITS
PER LOOP.

DESCRIPTION

The Model APSIS is a convenient plug-in unregulated +24 VDC power

supply designed to “load share” when connected in parallel with other +24
VDC unregulated systems with unusual power requirements due to sensor or
accessory loading (see Fig.1). It can also be used as a general purpose stand-
alone supply to power +24 VDC control circuits, sensors and accessories (see
Fig.2)
. In addition, two 20 mA Current Source outputs are available, each
capable of powering up to 16 Serial Communications units (see Fig.3). The
APSIS is available in 115 and 230 VAC ±10%, 50/60 Hz. primary supply (see
Ordering Information)
. Operating temperature range is -20°C to +50°C.

SPECIFICATIONS

1. POWER SOURCE: 2 versions, 115 VAC or 230 VAC ±10%, 50/60 Hz., 11

VA max. (see Ordering Information).

2. POWER OUTPUT: +24 VDC unregulated @ 200 mA max. current*,

Ripple = 1.5 V P-P max.

3. OUTPUT: Two 20 mA current sources, each capable of supplying 20 mA of

current for serial communication loops and powering up to 16 units per loop.

4. OPERATING TEMPERATURE: -20°C to +50°C (-4°F to +122°F)

* Maximum available output current derates to 175 mA with 1 source active

and 150 mA max. with both sources active.

MODEL APSIS -

Octal Plug-in Accessory Power Supply With 20 mA Current Sources

TYPICAL LOAD SHARING CONNECTION DIAGRAM

DIMENSIONS In inches (mm)

Mating
Sockets
Sold
Separately
(See
Ordering
Information)

FIGURE 1

TEMPERATURE MONITORING SYSTEM

A temperature monitoring process requires both remote

and control room indicators and datalogging capabilities.
An RTD (Resistance Temperature Detector) to 4 to 20 mA
Transmitter, provides a proportional 4 to 20 mA output
from the RTD input. Two Red Lion Controls “Loop
Powered Process Indicators” (Model LPPI)
are installed
in series in the “Loop” and scaled to provide Local and
Remote temperature displays. A Datalogger is also placed
in the “Loop” to provide a hard-copy of process
temperatures. Each device in the “Loop” has an associated
“voltage drop” as follows: RTD Transmitter = 9 VDC
drop; LPPI = 3 VDC x 2 units = 6 VDC drop; Datalogger
= 5 VDC drop. The total voltage drops in the “Loop” =
20 VDC. Therefore, RLC’s Model APSIS, with its +24
VDC Supply, is used to power this process “Loop”.

FIGURE 2

Bulletin No. APSIS-C
Drawing No. LP0184
Released 11/02

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion-controls.com

Advertising
This manual is related to the following products:

APS