DEDICATED HIGH DENSITY INPUT MODULES FOR THE

MODULAR CONTROLLER SERIES

MODELS AVAILABLE TO ACCEPT ±10 V, 0/4-20 mA,

THERMOCOUPLE AND RTD INPUTS

±10 V AND 0/4-20 mA INPUT VERSIONS FULLY SCALABLE

±10 V AND 0/4-20 mA INPUT VERSIONS AVAILABLE WITH 100

POINT LINEARIZATION

UNUSED INPUTS CAN BE DISABLED TO INCREASE OVERALL

READING RATE

IDEAL FOR DATA-ACQUISITION APPLICATIONS

AUTO ADDRESSING MINIMIZES CONFIGURATION TIME

CAN BE USED IN CONJUNCTION WITH ANY CS

SERIES MODULES

GENERAL DESCRIPTION

The Model CSTC, CSRTD, CSINI, and CSINV are 16-bit analog input

modules designed for use with the Modular Controller Series. These modules
provide a means of high-density signal measurement for data-acquisition
applications. The CSTC module accepts a wide range of thermocouple types,
while the CSRTD accepts various RTD inputs. The CSINI and CSINV accept
0/4-20 mA and ±10 V process signals, respectively.

The modules connect and communicate via a backplane connection to the

CSMSTR Modular Controller Series Master. The CSMSTR, equipped with serial
ports as well as an Ethernet port, allows the system to share data with PCs, PLCs,
and SCADA systems. The Master supports any combination of up to 16 CS series
modules, allowing a total of 128 signals to be monitored via a single Master.

Internal power management circuits allow the modules to be replaced while

power is applied, which reduces downtime. All configuration information is
stored locally within the module, as well as in the Master, so replacement
modules do not need to be configured.

The Modular Controller Series’ high density packaging and DIN rail

mounting saves time and panel space. The backplane connection provides power
and communication to the module and snaps easily onto standard top hat (T)
profile DIN rail.

CONFIGURATION

The Modular Controller Series is configured with Windows

®

compatible

Crimson

®

software. The software is an easy to use, graphical interface which

provides a means of configuration and commissioning of new systems, as well
as routine module re-calibration.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

Do not use the module to directly command motors, valves, or other actuators

not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the module. An independent and redundant
temperature limit indicator with alarm outputs is strongly recommended.

MODELS CSTC, CSRTD, CSINI, CSINV -
MODULAR CONTROLLER SERIES ANALOG INPUT MODULES

Bulletin No. CS8-K
Drawing No. LP0556
Released 06/12

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

CAUTION: Risk of Danger.

Read complete instructions prior to

installation and operation of the unit.

CAUTION: Risk of electric shock.

1

7

13

1.24

(126.5)

4.17 (105.9)

4.98

(31.5)

DIMENSIONS In inches (mm)

CC

US LISTED

US LISTED

UL

R

IND. CONT. EQ.

34AD

FOR USE IN HAZARDOUS LOCATIONS:

Class I, Division 2, Groups A, B, C, and D

CC

US

US

UL

R

LISTED

IND.CONT. EQ.

3PWL

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I,
DIVISION 2, GROUPS A, B, C, D, OR NON-HAZARDOUS
LOCATIONS ONLY