Red Lion CSPID User Manual

General description, Dimensions in inches (mm), Configuration

Advertising
background image

1

DEDICATED SINGLE AND DUAL PID MODULES FOR THE

MODULAR CONTROLLER SERIES

HOT-SWAPPABLE REPLACEMENT REDUCES DOWNTIME

AUTO ADDRESSING MINIMIZES CONFIGURATION TIME

FULLY ISOLATED DESIGN PROVIDES RELIABLE OPERATION

PID CONTROL WITH REDUCED OVERSHOOT

UNIVERSAL INPUTS ACCEPT TC, RTD, 0-10 V and 0/4-20 mA

SIGNALS

ON DEMAND AUTO-TUNING OF PID SETTINGS

DC ANALOG OUTPUT (OPTIONAL, CSPID1 ONLY)

HEATER CURRENT INPUT (OPTIONAL) ENSURES DETECTION

OF HEATER CIRCUIT FAILURE

WINDOWS

®

CONFIGURATION SOFTWARE

GENERAL DESCRIPTION

The Model CSPID series modules are full featured PID controllers designed

for use with the Modular Controller Series. The CSPID1 is a single loop

controller, while the CSPID2 is a dual loop controller. The design of the system

provides a true modular PID control platform for multi-zone control applications.

The modules can accept a wide range of thermocouple, RTD, 0-10 V, 0/4-20 mA

signals. With multiple discrete outputs, plus an optional analog output (CSPID1

only), the CSPID modules can perform virtually any combination of time-

proportioning or linear control for heat, cool, or heat/cool applications. The

discrete outputs may also be assigned to one of seven internal soft alarms. The

CSPID1’s optional linear output can be assigned to transmit virtually any

internal variable.

The CSPID modules connect and communicate via a backplane connection to

the CSMSTR Modular Controller Series Master. The CSMSTR, equipped with

serial ports as well as an Ethernet port, allows the system to share data with PCs,

PLCs, and SCADA systems. The Master supports any combination of up to 16

CS Series modules.

The CSPID modules are available with various discrete output combinations,

including relays, open drain MOSFETs, and triac outputs. For applications

requiring large loads to be controlled, several DIN rail mount relays are available.

The modules can operate in On/Off, P, PI, or PID control mode, and use an

on-demand Auto-Tune that establishes the tuning constants. The PID constants

may be fine-tuned through the serial or Ethernet interface. The modules employ

a unique overshoot suppression feature, which allows the quickest response

without excessive overshoot. The modules can also be operated in manual mode,

providing the operator with direct control of the output.

Internal power management circuits allow the modules to be replaced while

power is applied, which reduces downtime in the event of a relay failure. All

configuration information is stored locally within each module, as well as in the

Master, so replacement modules do not need to be configured.

The Modular Controller Series’ high density packaging and DIN rail

mounting saves time and panel space. The backplane connection provides power

and communication to the module and snaps easily onto standard top hat (T)

profile DIN rail.

CONFIGURATION

The Modular Controller Series is configured with Windows

®

compatible

Crimson

®

software. The software is an easy to use, graphical interface which

provides a means of communication configuration, as well as commissioning

and calibration of new systems.

ALARMS

Each loop within the modules has seven internal “soft” alarms, which can be

assigned to trigger any output. This includes four process alarms, two heater

current, and one input fault alarm.

ANALOG OUTPUT OPTION (CSPID1 ONLY)

The optional DC Analog Output (10 V or 20 mA) can be independently

configured and scaled for control or re-transmission purposes.

MODEL CSPID – MODULAR CONTROLLER SERIES PID MODULES

Bulletin No. CSPID1-J
Drawing No. LP0542
Released 12/12

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

1

7

13

1.24

(126.5)

4.17 (105.9)

4.98

(31.5)

DIMENSIONS In inches (mm)

CAUTION: Risk of Danger.

Read complete instructions prior to

installation and operation of the unit.

CAUTION: Risk of electric shock.

C

US LISTED

UL

R

IND. CONT. EQ.

34AD

For Model No. CSPID2S0, CSPID2SM, CSPID2T0, and CSPID2TM Only

FOR USE IN HAZARDOUS LOCATIONS:

Class I, Division 2, Groups A, B, C, and D

C

US

UL

R

LISTED

IND.CONT. EQ.

3PWL

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF

COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,

DIVISION 2
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I,

DIVISION 2, GROUPS A, B, C, D, OR NON-HAZARDOUS

LOCATIONS ONLY

Advertising