ALARM HYSTERESIS

The Hysteresis Value is either added to or subtracted from the alarm value,

depending on the alarm action selected. The same value applies to both alarms.

See the Alarm Action Figures at the beginning of this section for a visual

explanation of how alarm actions are affected by the hysteresis.

to



CHANGE COLOR

Select alarm(s) to change Input Display color intensity when appropriate

alarm(s) are triggered.

AL-3

AL-2

AL-1

ANY

OFF



Cl



ALARM 3 STANDBY

Standby prevents nuisance (typically low level) alarms after a power up.

After powering up the controller, the process must leave the alarm region (enter

normal non-alarm area of operation). After this has occurred, the standby is

disabled and the alarm responds normally until the next controller power up.

ALARM 3 VALUE

The alarm values are entered as process units or degrees. They can also be

entered in the Parameter or Hidden Loops. When the alarm is configured as

deviation or band acting, the associated output tracks the Setpoint as it is

changed. The value entered is the offset or difference from the Setpoint.

ALARM 3 RESET MODE

In Automatic mode, an energized alarm turns off automatically after the

Temperature/Process value leaves the alarm region. In Latched mode, an

energized alarm requires an 1 / 2 key or user input alarm reset to turn off. After

an alarm reset, the alarm remains reset off until the trigger point is crossed again.



Automatic



Latched



Standby on



Standby off



to



19

7.5 mOdule 7 - s

erial

C

OmmuniCaTiOns

p

arameTers

(

C

)

tYPE

dAtA

bAUd

COMUNICATIONS

TYPE

BAUD

RATE

DATA

BIT

7-SC

CNFP

PArb

PARITY

BIT

Addr

METER

ADDRESS

P

P

PARAMETER MENU

38K4



8



DATA BIT

NO



PARITY BIT

2400

600

400

1K2

3K4

7

NO

EvEN

Odd

BAUD RATE

Set the baud rate to match that of other serial communications equipment.

Normally, the baud rate is set to the highest value that all of the serial

communications equipment is capable of transmitting.

Select either 7 or 8 bit data word lengths. Set the word length to match that

of other serial communication equipment. If

rtU

is selected as the communication

type,

dAtA

defaults to 8.

Set the parity bit to match that of the other serial communications equipment

used.

247



METER ADDRESS

1

to

247

Select a Unit Address that does not match an address number of any other

device on the serial link.





COMMUNICATIONS TYPE



ModBus RTU

C

ModBus ASCII

Select the desired communications protocol.



3



b3

3

3

INPUT FAIL ALARM 3 ACTION



I3





Select the Alarm action in the event of a detected input failure (open TC/RTD

or shorted RTD).

Shaded parameters are programming/model dependent.