Red Lion TSC User Manual

Page 58

Advertising
background image

Display

Parameter

Range and Units

(Factory Setting

Value)

Description/

Comments

PSEt

Setpoint Profile

NO

Pr-1

Pr-2

Pr-3

Pr-4

PE-1

PE-2

PE-3

PE-4

(NO)

NO - Return to

CNFP

Profile 1

Profile 2

Profile 3

Profile 4

Time event output

for profile 1

Time event output

for profile 2

Time event output

for profile 3

Time event output

for profile 4

The parameters for the four profiles are the same. (Pn = profile 1, 2, 3, or 4)

PnCC

Profile n

cycle count

0-250

(0)

0 = off

250 = continuous

PnLn

Profile n link option

YES/NO

(NO)

Link if more than 8

ramp/soak phases

are required.

PnSt

Profile n power-on

status

Stop- Stop profile

CONt - Continue

profile

Strt - Start profile

(Stop)

Continue has

priority.

PnEb

Profile n error band

-999 to 9999

1 or .1 degree

(0)

0 = off. (+) Values

hold phases only

(-) values ramp and

hold phases

Pnr1

Profile n ramp rate

0.0 to 999.9

degrees/minute

(0.0)

0.0 = step (instant

ramp) -0.1 ends the

profile.

PnL1

Profile n setpoint

level 1

SPLO to SPHI

1 or .1 degree

(0)

Constrained to

setpoint limit

values.

PnH1

Profile n

hold time 1

0.0 to 999.9

minutes

(0.0)

0.0 = no hold

phase.

Program up to 8 ramp/hold phases. Profile ends when ramp = -0.1 or PnH8 is programmed.

Display

Parameter

Range and Units

(Factory Setting

Value)

Description/

Comments

Pnr8

Profile n ramp rate

8

0.0 to 999.9

degrees/minute

(0.0)

Same as ramp 1.

PnL8

Profile n setpoint

level 8

SPLO to SPH

1 or .1 degree

(0)

Same as setpoint

1.

PnH8

Profile n hold time

8

0.0 to 999.9

minutes

(0.0)

Same as hold 1.

Profile returns to “PSEt” stage.

The parameters for the four timed event outputs are the same. (Pn = Timed Event

Output for proflile 1, 2, 3, or 4.)

Pn 1

Event output

number 1 for profile

n

1F2F

1F2N

1N2F

1N2N

(1F2F)

Assign alarms to

timed event output

in alarm action.

F = OFF; N = ON

1 = AL1; 2 = AL2

Each event output has the same programmable options. Event updates end when profile ends.

Pn 16

Event output

number 16, for

profile n

1F2F

1F2N

1F2F

1N2N

(1F2F)

Assign alarms to

timed event output

in alarm action.

F = OFF; N = ON

1 = AL1; 2 = AL2

Event Output step returns to “PSEt” stage.

-56-

QUICK REFERENCE TABLE: CONFIGURATION PROFILE MODULE 8 (8-PR)