Red Lion PCU User Manual

Page 78

Advertising
background image

4. CONTROLS: Four front panel push buttons for modifying and setup of

controller functions and one external input for parameter lockout or other
functions.

5. SIGNAL INPUT:

Sample Period: 100 msec typ.
Response Time: 300 msec typ. (to within 99% of final value w/step input)
Signal Overdrive Threshold:

10 V Range: 13.00 V typ.
20 mA Range: 26.00 mA typ.

Signal Overdrive Response:

Main Control Output(s): Programmable preset output
Display: “SENS”
Alarms: Upscale drive
DC Linear: Programmable preset output

Normal Mode Rejection: 40 dB typ. @ 50/60 Hz (improves with
increased digital filtering).
Common Mode Rejection: 100 dB typ., DC to 60 Hz
Protection: Input overload 120 VAC for 30 seconds.
Range and Accuracy:

Signal
Range

Accuracy (% of

Unscaled Reading)

Maximum

Input

Input

Impedance

Resolution

0-10 VDC ±(0.15% + 3 mV + 1 LSD) 300 VDC

1 M

W

10 mV

0-20 mA DC ±(0.15% + 6

mA + 1 LSD) 200 mA DC

10

W

10

mA

6. OUTPUT MODULES [Optional] (For All Output Channels):

Relay:

Type: Form-C (Form-A with some models. See Ordering Information)
Rating: 5 Amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 HP @

120 VAC max. (inductive load)

Life Expectancy: 100,000 cycles at max. load rating. (Decreasing load

and/or increasing cycle time, increases life expectancy).

Logic/SSR Drive: Can drive multiple SSR Power Units.

Type: Non-isolated switched DC, 12 VDC typical
Drive: 45 mA maximum

Triac:

Type: Isolated, Zero Crossing Detection
Rating:

Voltage: 120 to 240 VAC

Max. Load Current: 1 Amp @ 35°C

0.75 Amp @ 50°C

Min. Load Current: 10 mA

Offstate Leakage Current: 7 mA max. @ 60 Hz
Operating Frequency: 20 to 400 Hz
Protection: Internal Transient Snubber, Fused

7. MAIN CONTROL OUTPUT:

Control: PID or ON/OFF
Output: Time proportioning or linear DC
Hardware: Plug-in, replaceable output modules
Cycle time: Programmable
Auto-tune: When selected, sets proportional band, integral time, and
derivative time values.
Signal Overdrive Action: Programmable

8. SECONDARY OUTPUT (Optional):

Control: PID or ON/OFF
Output: Time proportioning or linear DC
Hardware: Plug-in, replaceable output modules
Cycle time: Programmable
Proportional Gain Adjust: Programmable
Deadband Overlap: Programmable

9. LINEAR DC OUTPUT (Optional): With digital scale and offset,

programmable deadband and update time.
4 to 20 mA:

Resolution: 1 part in 3500 typ.
Accuracy:

±(0.1% of reading + 25 mA)

Compliance: 10 V

(500 W max. loop impedance)

0 to 10 VDC:

Resolution: 1 part in 3500 typ.
Accuracy:

±(0.1% of reading + 35 mV)

Min. Load Resistance: 10 K

W (1 mA max.)

Source: % output power, setpoint, deviation, or process value

(Available for OP1 or OP2, but not both.)

10. MOTORIZED VALVE POSITIONER (Optional):

Two Outputs: Valve open and valve close or Linear DC (optional)
Hardware: Plug-in, replaceable output modules
Three Inputs: Slidewire feedback, signal fail detect

(Isolated from main input)

Slidewire resistance: 100

W to 100 KW

-70-