Red Lion IFMR User Manual

Model ifmr - din-rail speed switch, Description, Safety summary

Advertising
background image

1

SIMPLE ON-LINE TRIP FREQUENCY SETTING (USING ACTUAL

INPUT SIGNAL OR FREQUENCY GENERATOR)

USER SETTABLE TRIP FREQUENCY FROM 0.1 Hz to 25 KHz

OVER-SPEED, UNDER-SPEED, AND ZERO-SPEED DETECTION

RELAY LATCHING, ALARM OVERRIDE, AND ALARM RESET

FUNCTIONS

PROGRAMMABLE INPUT CIRCUIT ACCEPTS OUTPUTS FROM

A VARIETY OF SENSORS

HYSTERESIS AND OFFSET FUNCTIONS AVAILABLE

85 to 250 VAC and 9 to 32 VDC VERSIONS AVAILABLE

INPUT AND RELAY STATUS INDICATION LED’S

MODEL IFMR - DIN-RAIL SPEED SWITCH

DESCRIPTION

The Model IFMR accepts a frequency input, and controls a single relay

(SPDT) based on the value of the input frequency. The Trip frequency can be
set to any value from 0.1 Hz to 25 KHz. The IFMR can be set to trip on
overspeed, or underspeed (including zero speed). Offset and hysteresis values
can be incorporated into the trip setting to eliminate output chatter. LED
indicators for both the Input signal and the Relay status are provided. Two
separate input connections for external push-buttons are also provided. One
external input overrides the trip detection function, and holds the relay in the
release state as long as the input is pulled to common. The other external input
clears a latched trip condition when pulled to common.

The IFMR utilizes a seven position DIP switch, a rotary switch, a push-

button and two indication LEDs to accomplish input circuit configuration,
operational parameter set-up, input signal, and relay status indication. The input
circuitry is DIP switch selectable for a variety of sources.

The indication LEDs are used during normal operation to display the input

signal and relay status of the IFMR. These LEDs are also used to provide visual
feedback to the user of the current parameter settings during parameter set-up.

The IFMR operates in one of six output modes, as selected by the user. The

programmable Minimum Response Time provides optimum response vs. input
filtering for any input frequency. The offset and hysteresis settings provide
flexible adjustment of the relay trip and release points.

The unit is equipped with a universal mounting foot for attachment to

standard DIN style mounting rails, including top hat profile rail according to EN
50 022 - 35 x 7.5 and 35 x 15, and G profile rail according to EN 50 035 - G32.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

WARNING: SPEED SWITCHES MUST NEVER BE USED AS

PRIMARY PROTECTION AGAINST HAZARDOUS OPERATING
CONDITIONS. Machinery must first be made safe by inherent design,

or the installation of guards, shields, or other devices to protect personnel in
the event of a hazardous machine speed condition. The speed switch may be
installed to help prevent the machine from entering the unsafe speed.

SPECIFICATIONS

1. POWER:

AC Powered Versions: 85 to 250 VAC; 48 to 62 Hz; 5.5 VA
DC Powered Versions: 9 to 32 VDC; 2.0 W

Power Up Current: Ip = 600 mA for 50 msec max.

2. SENSOR POWER: (AC version only) +12 VDC

25% @ 60 mA max.

3. OPERATING FREQUENCY RANGE: 0 Hz to 25 KHz
4. SIGNAL INPUT: DIP switch selectable to accept signals from a variety of

sources, including switch contacts, outputs from CMOS or TTL circuits,
magnetic pickups, and all standard RLC sensors.
Current Sourcing: Internal 1 K

 pull-down resistor for sensors with current

sourcing output. (Max. sensor output current = 24 mA @ 24 V output.)

Current Sinking: Internal 3.9 K

 pull-up resistor for sensors with current

sinking output. (Max. sensor current = 3 mA.)

Low Bias: Input trigger levers V

IL

= 0.25 V, V

IH

= 0.75 V; for increased

sensitivity when used with magnetic pickups.

Hi Bias: Input trigger levels V

IL

= 2.5 V, V

IH

= 3.0 V; for logic level signals.

Max. Input Signal: ±90 V; 2.75 mA max. (with both Current Sourcing and

Current Sinking resistors switched off).

ORDERING INFORMATION

M1865G

IFMR

12

3

46

5

7

9

8

10

12

11

OUT

IN

120/240

VAC

5 AMP

5 AMP VAC

120/240

OVERRIDE

+12V

60mA

ALARM

A

LARM

RESET

INPUT

COMM

SEE THE IFMR BULLETIN

ON

85-250 VAC 50/60HZ 5.5W

CFG0

SRC.

LOGIC

MODE

CFG2

CFG1

SINK

FOR SET-UP INSTRUCTIONS.

~

AC

~

AC

4.20 REF

1.08

3.12

(27.5)

(106.7)

(79.2)

M1864G

OUT

IN

0

9

8

7 6 5 4

3

2

1

IFMR

S

T

A

T

U

S

!

RED LION CONTROLS

SPEED CONDITIONS.

SEE THE IFMR BULLETIN.

WARNING: THIS DEVICE MUST NOT

BE USED AS PRIMARY PROTECTION

AGAINST HAZARDOUS OPERATING

MADE IN U.S.A.

YORK, PA.

DIMENSIONS In inches (mm)

MODEL NO.

DESCRIPTION

PART NUMBERS FOR AVAILABLE

SUPPLY VOLTAGES

9 to 32 VDC

85 to 250 VAC

IFMR

Speed Switch

IFMR0036

IFMR0066

Bulletin No. IFMR-J
Drawing No. LP0341
Released 04/09

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

UL Recognized Component,
File # E137808

CAUTION: Risk of Danger.

Read complete instructions prior to

installation and operation of the unit.

CAUTION: Risk of electric shock.

Advertising