Red Lion RLY5 User Manual

Model rly5 - solid state power unit, General description, Specifications

Advertising
background image

SWITCHES UP TO 45 AMPERES @ 240 VAC

LOW LEVEL DC INPUT CONTROL SIGNAL (3-32 VDC)

OPTICALLY-ISOLATED OUTPUT

ZERO VOLTAGE TURN-ON, ZERO CURRENT TURN-OFF FOR

REDUCED RFI

INTERNAL SNUBBERS TO REDUCE FALSE TRIGGERING

RELATED TO HIGH dv/dt APPLICATIONS

SUPPLIED WITH HIGH EFFICIENCY HEATSINK FOR SUPERIOR

THERMAL and SURGE CURRENT RATINGS

GENERAL DESCRIPTION

The SSR Power Unit is a solid state relay which can switch load currents up

to 45 Amperes @ 240 VAC. The unit interfaces directly with a SSR Drive

Module (OMD00003). The input and output terminals are isolated from each

other to eliminate ground loops and noise problems. The unit features a zero

voltage turn-on and a zero current turn-off detector to minimize radiated RFI

when switching. An internal snubber minimizes inrush currents and guards

against false triggering of the output; related to high dv/dt applications. A low

DC control signal of +3 to +32 VDC is all that is needed for the switching

operation. The solid state switch, highlighted by the inverse-parallel SCR

output, provides a greatly increased operational life over a mechanical relay by

avoiding the usual relay contact problems: arcing, bouncing, mechanical

failure, etc. The solid state relay is shipped mounted to the high efficiency

heatsink for immediate installation.

MODEL RLY5 - SOLID STATE POWER UNIT

SPECIFICATIONS

OUTPUT SPECIFICATIONS

1. Operating Voltage Range: 50-280 VAC RMS

2. Operating Frequency Range: 47-63 Hz

3. Maximum Continuous Load Current: See Thermal Rating Code

4. Maximum Surge Load Current: See Peak Surge Current Curve

5. Minimum Load Current: 40 mA RMS

6. Maximum Off-State Leakage Current: 10 mA RMS

7. Maximum Transient Voltage: 600 V peak

8. Maximum Output Voltage Drop: 1.6 V peak

9. Power Dissipation at Full Load: 50 Watts

10. Maximum I

2

T: 1600A

2

sec

(For Fusing Purposes, t = 8.3 msec)

11. Minimum Off-State dv/dt protection: 500 V/usec

INPUT SPECIFICATIONS

(Use with RLC SSR Drive Module, OMD00003)

1. Control Voltage Range: 3 to 32 VDC

2. Maximum Turn-on Voltage: 3 VDC

3. Minimum Turn-off Voltage: 1 VDC

4. Maximum Reverse Voltage: -32 VDC

5. Minimum Input Impedance: 1500 Ω

6. Maximum Turn-on/Turn-off time: 8.3 msec

GENERAL SPECIFICATIONS

1. Isolation (Input to Output to Base): 4000 V RMS

2. Insulation Resistance: 10 GΩ

3. Operating Temperature Range: -30° to +75°C

4. Storage Temperature Range: -40° to +120°C

Bulletin No. RLY5-C
Drawing No. LP0254
Released 06/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

2.62

(66.5)

4.75 (121)

4.56 (116)

CENTERS FOR #8 SCREWS

4.50

5.50

(114)

(140)

0.20 (TYP.)

(5.1)

(5.5)

0.22 (TYP.)

DIMENSIONS In inches (mm)

MODEL

DESCRIPTION

PART NUMBER

RLY5

SSR Power Unit

RLY50000

ORDERING INFORMATION

INSTALLATION

It is recommended to mount the unit outside of an enclosure in an area where

there is unrestricted air flow. The unit should always be mounted with the fins

in a vertical position to maximize heat dissipation. If mounting the unit inside

an enclosure, the internal temperature of the enclosure will normally be higher

than the surrounding area and must be accounted for. At full rated load, the unit

will dissipate 50 watts and achieve a case temperature in excess of 90°C. In all

installations, it is important to allow at least two inches around the power unit

for proper ventilation.