CONNECTION AND OPERATION

INSTRUCTIONS

PROTECTION

The device must be installed in accordance with the specifications of EN

60950.

It must be possible to switch off the device using a suitable disconnecting

device outside the power supply. For example, primary side line protection
could be used.

In case of DC applications it is necessary to connect in series an adequate fuse.

RAIL MOUNTING

The power supply unit can be snapped onto all mounting rails in accordance

with EN 50022-35. Installation should be made horizontally (input terminal
blocks below).

CABLE CONNECTION

The device is equipped with COMBICON plug connectors.
This easy-to assemble connection method allows devices to be exchanged

easily and the electrical connection to be visibly isolated.

Connecting Cables:

Cable cross sections from 0.2 to 2.5 mm

2

rigid (solid)/flexible (stranded)

(AWG 24-14) may be used.

To maintain UL, use copper cable rated for an operating temperature of

75°C/170°F.

For Reliable And Touch-proof Contacts:

Strip the connection ends (7 mm - See Figure).

INPUT

The input connection is made by the screw

connections “L(+)” and “N(-)” (torque 0.5 Nm) on the
COMBICON plug connection.

For device protection, there is an internal fuse.

Additional device protection is not necessary.

Recommended backup fuses are power circuit-

breakers 6 A or 10 A, charactistic B (or identical
function). In DC applications, a suitable backup fuse
must be wired in.

If the internal fuse is triggered, there is most
probably a malfunction in the device. In this
case, the device must be inspected in the
factory

!

OUTPUT

The 24 VDC connection is made by the screw connections “+” and

“-” (torque 0.5 Nm) on the COMBICON plug connection. At the time of
delivery, the output voltage is 24 VDC. The output voltage can be set from 22.5
to 28.5 VDC on the potentiometer.

The device is electronically protected against short circuits and idling. In the

event of an error, the output voltage is limited to max 35 VDC.

Function Monitoring

For function monitoring, there is the active DC OK switching output and the

DC OK LED.

The 24 VDC signal is measured between the “DC OK” and “-” connection

terminal blocks and can be loaded with 20 mA maximum. This signal output
indicates that the output voltage has fallen below 21.5 VDC when “active high”
changes to “low”.

The DC OK signal is isolated from the power output.

Output Characteristic Curve

The device functions following the U-I characteristic curve. Under load, the

operating point follows this curve. In the event of a short circuit or overload, the
output current is limited to I

BOOST

. The secondary voltage is reduced until the

short circuit on the secondary side has been remedied.

Thermal Behavior

In the case of ambient temperatures above +60ºC, the output capacity has to

be reduced by 2.5% per Kelvin increase in temperature.

From +70°C or a thermal overload, the device reduces the output power for

its own protection, and returns to normal operation when it has cooled down.

Caution: Danger! Never work on live equipment!
Caution: When the device is opened, a dangerous voltage may remain
at the electrolytic capacitors for up to 2 minutes after shutdown!

The installation must be performed by a specialist in accordance with
the requirements of EN 60950.
For vertical installations we recommend a minimum spacing of 5 cm
(1.97 in.) between other modules and this power supply to ensure
sufficient convection.
No minimum spacing is required for horizontal alignment.
The mains feed line must have an appropriate fixing or strain relief
outside of the device.
The supply-side installation and the connection via screw terminal
blocks must be done in a way that ensures protection against electric
shock.

ORDERING INFORMATION

STATUS 1

STATUS 2

Green LED “ DC OK”

on

off

Active DC OK switching
output

U = +24 V
(in reference to “-”)

U = 0 V
(in reference to “-”)

Status

Normal operation of the
power supply.
U

OUT

> 21.5 V

U

OUT

< 21.5 V

• Secondary consumer

short-circuit or overload

• No mains voltage or

device faulty

U

[V]

U 24

60°C

40°C

I

I

[A]

OUT

N

I

OUT

BOOST

N

OUTPUT

PSDR1

24 VDC @ 1A

PSDR0100

PSDR2

24 VDC @ 2A

PSDR0200

PSDR4

24 VDC @ 4A

PSDR0400

PART NUMBER

MODEL NO.

1

1.3

PSDR0200

2

4

PSDR0400

4

6

PSDR0100

I

BOOST

I

N

Red Lion Controls
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839

Red Lion Controls AP

31, Kaki Bukit Road 3,

#06-04/05 TechLink

Singapore 417818

Tel +65 6744-6613

Fax +65 6743-3360

Red Lion Controls BV

Printerweg 10

NL - 3821 AD Amersfoort

Tel +31 (0) 334 723 225

Fax +31 (0) 334 893 793

Advertising