Operating and installation instructions

Pneumatic actuators - FA160-800

9.0 Troubleshooting

In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.

If malfunctions cannot be eliminate with the help of the following table „10.0
Troubleshooting table
“, the supplier or manufacturer should be consulted.

10.0 Troubleshooting table

ATTENTION !
It is essential that the safety regulations are observed when identifying faults.

ATTENTION !
- read point 7.0 and 8.0 prior to
dismantling and repair work !
- read point 6.0 before restarting the plant !

Fault

Possible causes

Corrective measures

Actuator unit does not move

No compressed air on the control
pressure line

Discern the causes and remedy

Actuator unit has been improperly
installed

Check the actuator’s operating
mode and connect to the control
pressure line in accordance to this
operating mode
(refer to item 5.0)

The rolling diaphragm is defect

Replace the rolling diaphragm and
springs

There is not enough positioning
force available

Wrong actuator

Install a suitable actuator
(refer to item 4.5)

Control air pressure too low

Adjust the control air pressure as
described in 4.5.2; note the
permissible closing pressures!

The ventilation is plugged and the
air cannot escape from the actuator
unit

Screw cap must be disengaged