0 troubleshooting table – ARI Armaturen STEVI 451 EN User Manual

Page 20

Advertising
background image

Page 20

Rev. 0040306000 0410

Operating and installation instructions

3-way control valves - STEVI

®

450 / 451

9.0 Troubleshooting table

ATTENTION !
- read item 10.0 and 11.0 prior
to dismantling and repair work!
- read item 6.0 bef
ore restarting the plant !

Fault

Possible cause

Corrective measures

No flow

Valve closed

Open valve (using actuator)

Flange covers not removed

Remove flange covers

Little flow

Valve not sufficiently open

Open valve (using actuator)

Dirt sieve clogged

Clean / replace sieve

Piping system clogged

Check piping system

Kvs value of valve unsuitable

Fit valve with higher Kvs value

Stem moves in jerks.

Stuffing box sealing too tight
(for valves with graphite packings)

Slacken screw joint (pos. 42/20.17) or
hexagon nuts (pos. 24) slightly;
valve must not start leaking!

Valve plug slightly seized owing to solid
dirt particles

Clean internals, smooth rough spots.

Stem or plug cannot be
moved.

Seatring and plug clogged with dirt;
especially with V-port and perforated
plugs

Clean seatring and plug with suitable
solvent

Valve plug seized in seatring or guide
owing to deposits or dirt in medium

Replace plug and seatring; use parts
made from different material if neces-
sary

Stem leaking.

PTFE V-ring unit damaged or worn

Replace ring pack; refer to item 7.2

In valves with packed stuffing boxes
tighten screw joint (pos. 42)

Tighten screw joint (pos. 42) or hex.
nuts (pos. 24); replace packing if nec-
essary; refer to item 7.1.2

Bellows defective in valves with bellow
seal

Replace bellows unit; refer to item
7.1.3

Leakage too high when
valve is closed.

Sealing surfaces of plug eroded or worn Replace plug; refer to item 7.2
Sealing edge of seatring damages or
worn

Replace seatring; refer to item 7.2

Seatring and/or plug dirty.

Clean internal parts of the valve

Pneumatic actuator not completely
vented; spring force not fully effective

Vent actuator air chamber completely

Actuator not powerful enough

Install more powerful actuator;
check service data

Stem “hammers”.

flow in the closing direction

Compare the plug operation (mixing- or
diverting plug) with the application and
if necessary exchange the fittings or
increase actuator force